12.5 Electrical data

Power supply (switching network section)
Electrical safety
Power consumption
Data backup
Electrical connection
- Cross-sectional area
- Stranded wire with
With UL applications
Tightening torque
Electromagnetic compatibility
Emitted interference
Immunity

12.6 Housing

Type of housing
Color
Mounting depth
Mounting position
Degree of protection
Weight
- RWF50.2
- RWF50.3
User Manual RWF50...
12 Technical data
AC 110...240 V +10/-15%
48...63 Hz
To DIN EN 60730, part 1
Overvoltage category II
Degree of contamination 2
Max. 16 VA
EEPROM
At the rear via screw terminals
0.25...1.5 mm² fine-wired
- Ferrules to DIN 46228
- Pin-type cable socket to DIN 46231
- Crimp-type cable socket in fork-form for
M3 thread (dimensions to DIN 46237)
Use of the cable lug or ferrules to
UL486A-B (UL listed or recognized)
0.5 Nm
DIN EN 61326-1
Class B
Meeting industrial requirements
Made of Makrolon for control panel
mounting to DIN IEC 61554
(use in indoor)
Light-grey RAL7035
92 mm
Optional
To DIN EN 60529
Front side IP66
Rear IP20
(Fully equipped)
Approx. 170 g
Approx. 168 g