Controller Cntr - Siemens RWF50.3 User Manual

Compact universal controllers
Table of Contents

Advertisement

Parameter
Controller type
CtYP
Controller type
Operating action
CACt
Control direction
Setpoint limitation start
SPL
Setpoint limitation low
Setpoint limitation end
SPH
Setpoint limitation high
Self-optimization
Lower working range limit
oLLo
Lower operation range limit
Upper working range limit
oLHi
Upper working range limit
Building Technologies Division
Infrastructure & Cities Sector

8.2 Controller Cntr

Here, the type of controller, operating action, setpoint limits and presettings for self-
optimization are selected.
ConF  Cntr 
Value/
Description
selection
1
3-position controller (RWF50.2)
2
Modulating controller (RWF50.3)
1
Heating controller
0
Cooling controller
(1)
(0) = cooling controller:
The controller's angular positioning (Y) is >0 when the actual value
(x) lies above the setpoint (w)
(1) = heating controller:
The controller's angular positioning (Y) is >0 when the actual value
(x) lies below the setpoint (w)
-1999...
+9999
Setpoint limitation prevents values from being entered outside the
defined range.
-1999...
+9999
0
Free
1
Locked
Self-optimization can only be disabled or enabled via the ACS411
setup program
If disabled via ACS411 PC software, self-optimization cannot be
started via the controller's buttons
Setting in the ACS411 setup program
 Controller  Self-optimization
Self-optimization is also disabled when the parameter level is
locked
-1999...
+9999
-1999...
+9999
User Manual RWF50...
8 Configuration ConF
(0)
7866d14/0512
Note!
If the setpoint with the respective hysteresis exceeds the
upper working range limit, the switch-on threshold is
substituted by the working range limit.
Note!
If the setpoint with the respective hysteresis drops below
the lower working range limit, the switch-off threshold is
substituted by the working range limit.
43/64