Changing the setpoints
Timeout
34/64
Building Technologies Division
Infrastructure & Cities Sector
6.3 User level
This level is started from the basic display.
Setpoints SP1, SP2 or dSP can be altered.
The values of InP (analog input) and Y (current angular positioning between 0...100%)
can be displayed.
*
From the basic display, press
*
so that SP1 appears
Press
Enter
*
and SP1 flashes
Press
Enter
*
Press
or
to adjust the required setpoint and press
Timeout after about 180 seconds.
Note!
If the setpoint is not stored, the basic display changes after the timeout
former setpoint is maintained.
The value changes only within the permitted range.
User Manual RWF50...
6 Operation
so that OPr appears
Enter
to confirm
Enter
tout
and the
CC1U7866en
25.07.2014