Connecting
3.4 Programming the Transmitter
Select Pipe Configuration
1. Scroll down to [Pipe Config] and press the <Right Arrow>.
2. Select a configuration that approximates the conditions upstream of your sensor
3. Press <ENTER> to save selection.
4. Press the <Left Arrow> and return to the main menu.
Table 3- 2
Pipe Configuration Option List Definitions
Options
Fully Developed
Fully developed flow, as would be expected for very long straight pipe runs or installation downstream
of a flow condition.
1 Elbow
Single 90 degree Elbow upstream of sensor installation.
Dble Elbow+
Double out-of-plane Elbows upstream of sensor installation.
Dble Elbow-
Double in-plane Elbows upstream of sensor installation.
Valve
Not available at this time.
Expander
Pipe expansion upstream of sensor installation.
Reducer
Pipe reduction upstream of sensor installation.
Norm Entry
Not available at this time.
Header Inlet
Header or pipe manifold upstream of sensor installation.
Intrusions
Not available at this time.
34
mounting location. (Refer to the definitions below.)
Use this menu cell to enter the number of pipe
diameters between the upstream configuration
and the Sensor installation.
Use this menu cell to select the pipe configuration
that most accurately represents the upstream pipe
condition.
Definitions
FUS1010 IP65 NEMA 4X & IP66 NEMA 7 Quick Start
Operating Instructions, 01/2013, A5E03086486-AC