Output Disable Switch; Pulling The I/O Module In Runtime - Siemens SIMATIC ET 200SP HA Equipment Manual

Hide thumbs Also See for SIMATIC ET 200SP HA:
Table of Contents

Advertisement

Description
The following accessories are available:
• Labeling strips
• Color-coded labels
• Reference identification label
• Shield connector
• Terminal blocks
4.3

Output disable switch

Definition
The output disable switch switches the NO contact of the I/O module load-free.
NOTICE
Dangerous plant conditions possible (disconnect the load)
If you want to pull the I/O module in runtime, you have to press the output disable switch for
3 seconds so that the NO contact for the I/O module is load-free.
Pulling the I/O module in runtime (Page 13)
4.4

Pulling the I/O module in runtime

Requirement
The normally closed contacts are closed.
Procedure
Press the output disable switch for 3 seconds.
Note
Pressing the output disable switch interrupts any ongoing firmware update. A firmware update
cannot be performed when the device is deenergized.
Result
The I/O module is load-free.
RQ 4x120VDC-230VAC/5A CO HA
Equipment Manual, 07/2022, A5E39389042-AF
Product overview
4.4 Pulling the I/O module in runtime
13