Technical specifications
Technical specifications of the RQ 4x120VDC-230VAC/5A CO HA
Article number
General information
Product type designation
Firmware version
•
Usable terminal block
Color code for module-specific color identifica‐
tion plate
Product function
•
Engineering with
•
•
•
•
Redundancy
•
Supply voltage
Rated value (DC)
permissible range, lower limit (DC)
permissible range, upper limit (DC)
Reverse polarity protection
Input current
Current consumption (rated value)
Current consumption, max.
Power loss
Power loss, typ.
Address area
Address space per module
•
Switching frequency
•
•
Relay outputs
•
RQ 4x120VDC-230VAC/5A CO HA
Equipment Manual, 07/2022, A5E39389042-AF
FW update possible
I&M data
STEP 7 TIA Portal configurable/integrated
from version
STEP 7 configurable/integrated from version
PCS 7 configurable/integrated from version
PROFINET from GSD version/GSD revision
Redundancy capability
Address space per module, max.
with inductive load, max.
on lamp load, max.
Number of relay outputs
6DL1132-6HD50-0PK0
RQ 4x120 V UC ... 230 V AC/5 A CO HA
V1.0
Yes
TB type K0
CC40
Yes; I&M0 to I&M3
V16
V5.6
V9.0
GSDML V2.3
No
24 V
19.2 V
28.8 V
Yes
50 mA; At 24 V and energized changeover coils
60 mA; At 19.2 V and energized changeover coils
2.8 W; At 24 V, energized changeover coils and 5 A
current across each changeover contact
1 byte; + 1 byte for QI information
0.5 Hz
2 Hz
4
8
27