Specifications
Notes
The output power is derated –5 W/°C above 45 °C.
The combined loading on +5 VDC and +3.3 VDC must not exceed 112 W.
For AC powered applications, the combined loading must not exceed 145.6 W.
Chassis Cooling
NI PXI-1036/PXI-1036DC User Manual
Power disconnect ....................................The DC power cable provides
DC Output
DC current capacity (I
Voltage
+3.3 V
+5 V
+12 V
–12 V
Overcurrent protection............................All outputs protected from short
Overvoltage protection ...........................All outputs protected from
Per slot cooling capacity.........................25 W
Slot airflow direction ..............................P1 to P2, bottom of module
main power disconnect. The
front-panel power switch controls
the internal chassis power supply
that provides DC power to the
CompactPCI/PXI backplane.
)
MP
circuit and overload
overvoltage. Cycle the primary
power and front power switch to
restart.
to top of module
A-6
0–50 °C
12 A
17 A
2 A
0.8 A
ni.com