Starting The Bacnet Tcp/Ip Board With The Factory Settings - Mitsubishi Electric MEHITS MANAGER 3000+ Interface Manual

Table of Contents

Advertisement

IM_MANAGER3000+_TC02_REV00_04_21_EN
3. Click "Connections". Another window appears
4. Click "LAN settings"
5. Disable the proxy server
6. Press Ok to close the windows
Figure 3.7: demonstration of elimination of "proxy" network device
3.7.2

Starting the BACNET TCP/IP board with the factory settings

1. Switch on the W3000 + controller
2. Make sure that both the LEDs of the
Figure 3.8: display of leds presents on the connector
INFORMATION:
The choice as to whether to activate factory settings or user settings can only be made when starting the
board. The
BACNET TCP/IP
3.
As soon as the Status LED turns on GREEN immediately after restart, hold down the button to activate the
factory settings
4. If the button is held down, after about 20 seconds the Status LED will turn RED, flashing slowly three times.
Release the button during these 3 flashes
5. After the 3 red flashes, the Status LED turns GREEN and, if the procedure has been performed correctly, the Status LED will confirm the button
has been pressed and released by rapidly flashing RED 3 times and will then turn steady GREEN for about 1 minute (completion of the start phase).
Once the start phase is complete, the Status LED will start flashing: the BACNET TCP/IP board will be effectively running
In this way, the BACNET TCP/IP board will not use the "User" set communication configuration parameter values, but rather the following factory
values:
IP address: 172.16.0.1
Subnet mask: 255.255.0.0
INFORMATION:
These values will remain active until the BACNET TCP/IP BOARD IS RESTARTED.
After restart, the BACNET TCP/IP board will return to the "User" configuration values.
It is recommended that the network communication parameters are configured immediately
MEHITS S.p.A. ● INTERFACE MANUAL
BACNET TCP/IP
board connector light up within a few seconds
board restarts whenever it is turned on
Version 02 - Translation of the original instructions
20