Technical Data; Installation; Operation - Viking QUICK RESPONSE ELO VK377 Technical Data Manual

Pendent sprinkler storage-density/area
Table of Contents

Advertisement

Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

4. INSTALLATION

Refer to appropriate NFPA, FM Global, and/or any other applicable installation standards.

5. OPERATION

During fire conditions, when the temperature around the sprinkler reaches its operating temperature, the heat-sensitive liquid in the
glass bulb expands, causing the bulb to shatter, releasing the pip cap assembly. Water flowing through the sprinkler orifice strikes
the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
Viking Sprinkler Model VK377 is available through a network of domestic and international distributors. See The Viking Corporation
web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
Size
Sprinkler
Base Part
NPT
BSP
No.
Inch
mm
08337
3/4
20
17489
1/2
15
Example: 08337MB/W = VK377 with White Polyester Finish and 155 °F (79 °C) Nominal temperature rating. This sprinkler is to be
installed into an area with a maximum ambient temperature of 100 °F (38 °C) meaning if the area will experience temperatures above
the maximum ambient rating, you shall use a higher temperature-rated sprinkler.
Accessories
Sprinkler Wrenches (see Figure 1):
A. Standard Wrench: Part No. 05118CW/B (available since 1981).
B. Socket Wrench (for recessed or coated sprinklers): Part No. 11663W/B
Sprinkler Cabinet:
A. Up to 6 sprinklers: Part number 01724A (available since 1971).
B. 6-12 Sprinklers: Part number 01725A (available since 1971).
Footnotes
Where "-" is shown, insert the desired Temperature Rating suffix.
1.
Requires a 1/2" ratchet which is not available from Viking.
2.
Based on NFPA 13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
3.
Jurisdiction. Refer to specific installation standards.
UL Listed as corrosion resistant.
4.
FM Approved as a corrosion resistant.
5.
The corrosion resistant coating has passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These tests cannot and
6.
do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed
environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway.
Form No. F_030993
22.04.14

TECHNICAL DATA

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
TABLE 1: ORDERING INFORMATION
Instructions: Using the sprinkler base part number,
(1) add the suffix for the desired Finish
(2) add the suffix for the desired Temperature Rating.
1: Finishes
Description
Suffix
Brass
A
Chrome
F
White Polyester
M-/W
4,5,6
Black Polyester
M-/B
4,5,6
ENT
JN
4,5,6
Rev 22.1
2: Classifications and Temperature Ratings
Nominal
Classification
1
Rating
Ordinary
155 °F (68 °C)
Intermediate
175 °F (79 °C)
Intermediate
200 °F (93 °C)
High
286 °F (141 °C)
(available since 2001).
2
QUICK RESPONSE
ELO PENDENT
SPRINKLER VK377
(STORAGE-DENSITY/AREA)
Max. Ambient
Bulb
Ceiling
Color
Temperature
Red
100 °F (38 °C)
Yellow
150 °F (65 °C)
Green
150 °F (65 °C)
Blue
225 °F (107 °C)
Page 2 of 6