Trane 4YCC4024E1060 Installation And Operation Manual page 31

Single packaged gas/electric 13.4 seer2 convertible, 2 - 5 ton
Table of Contents

Advertisement

COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.
TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB
TEMPERATURE, OUTDOOR TEMPERATURE, DISCHARGE AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1);
LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN.
EXAMPLE: (1) OUTDOOR TEMP. 82 F.
(2) INDOOR WET BULB 67 F.
(3) AT INTERSECTION
(4) DISCHARGE PRESSURE @ 1200 CFM CFM IS 326 PSIG. DISCHARGE PRESSURE SHOULD BE +/- 10 PSI OF CHART
(5) SUCTION PRESSURE @ 1200 CFM CFM IS 144 PSIG.
18-EB40D1-1C-EN
Figure 11. Pressure Curve – 4YCC4036E1
Cooling
500
INDOOR ENTERING
WET BULB CURVES
TOP TO BOTTOM
71, 67, 63 AND 59 DEG
450
400
(3)
(4)
350
300
250
200
40
60
80
OUTDOOR TEMPERATURE (Degree F)
170
INDOOR ENTERING
165
WET BULB CURVES
TOP TO BOTTOM
160
71, 67, 63 AND 59
DEG F.
155
150
(3)
145
140
(5)
135
130
125
120
115
(1)
110
40
60
80
OUTDOOR TEMPERATURE (Degree F)
(2)
100
120
(2)
100
120
ACTUAL:
SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART
DWG.NO. 4YCC4036E1
U U n n i i t t S S t t a a r r t t u u p p
31