2-2-2-2. Temperature Upper and Lower Limit Setting
Set the temperature upper and lower limit setting of "Auto", "Cool/Dry", and "Heat".


4
3
5
No.
Item
Set temperature "Enable" / "Disable"

"Auto" upper limit

"Auto" lower limit
3
"Cool/Dry" upper limit
4
"Cool/Dry" lower limit
5
"Heat" upper limit
6
"Heat" lower limit
7
* The temperature upper and lower limit that can be set may differ depending on the registered indoor unit.
2-2-2-3. Remote Controller Prohibition Setting
Set the prohibited operations of remote controller.

No.
Item
Selected status

En-20
6
7
Sets "Enable" or "Disable" of upper and lower limit setting. Select from
"Enable" or "Disable".
Sets the "Auto" upper limit with 0.5ºC (1ºF) increments.
Range: 18.0 to 30.0ºC (64 to 88ºF)
Sets the "Auto" lower limit with 0.5ºC (1ºF) increments.
Range: 18.0 to 30.0ºC (64 to 88ºF)
Sets the "Cool/Dry" upper limit with 0.5ºC (1ºF) increments.
Range: 18.0 to 32.0ºC (64 to 91ºF)
Sets the "Cool/Dry" lower limit with 0.5ºC (1ºF) increments.
Range: 18.0 to 32.0ºC (64 to 91ºF)
Sets the "Heat" upper limit with 0.5ºC (1ºF) increments.
Range: 10.0 to 30.0ºC (48 to 88ºF)
Sets the "Heat" lower limit with 0.5ºC (1ºF) increments.
Range: 10.0 to 30.0ºC (48 to 88ºF)
Switches between enabled and disabled state by checking the checkbox.
(When checked, the setting is prohibited.)
"All", "On/Off", "On", "Mode", "Temp", "Timer", and "Filter Reset" can be set
to prohibited state.
When "All" is checked, other checkboxes are disabled.
Description