Carrier EnergyX 48HC Supplemental Installation Instructions page 12

Target national account system factory installed energy recovery 48/50hc weathermasterr commercial rooftop units 12.5 nominal ton units with puron r-410a refrigerant and i/o flex 6126 controls
Table of Contents

Advertisement

Value
Expanded Text
OAU_RUN
OAU System Run State
OAU_MODE
OAU Operating Mode
OAU_VER
OA Unit Software Version
ACTOACFM
Actual Outside Air CFM
ACTEXCFM
Actual Exhaust Air CFM
CMDOACFM
Command Outside Air CFM
CMDEXCFM
Command Exhaust Air CFM
OAU_LAT
OAU Leaving Air Temp
OAU_EXAT
OAU Exhaust Air Temp
OAU_BP
Building Pressure
OAUWHEEL
OAU Wheel Speed
OAFANSPD
OAU OA Fan Speed
OAUPESPD
OAU Exhaust Fan Speed
OAHEATER
OAU Tempering Heater
OAUALRM1
OAU Motor Failure Alarm
OAUALRM3
OA Low CFM Alarm
OAUALRM4
OAU Alarm
*
Requires an Economizer which is not available for Target EnergyX units at this time.
Table 4 – Status Points - - ERV Writes these Values
Range
1=AUTO
2=OFF
3=TEST
0=Off
1=ERV (DCV)
2=Free Cooling*
3=OA Tempering
4=Defrost
5=Test
6=Ext. Mode 1
7=Ext. Mode 2
8=Ext. Mode 3
0 to 9999
0 to 32000
0 to 32000
0 to 32000
0 to 32000
xxx.x
xxx.x
--- 0.25 to 0.25
0 to100
0 to100
0 to100
0 to 100
Off/On
Off/On
Off/On
Units
High level ERV state
ERV's current operating mode
Active EXCB software version
CFM
Real Time CFM being brought in
CFM
Real Time CFM being exhausted
CFM
Commanded CFM to bring in
CFM
Commanded CFM to exhaust
° F
Air temperature leaving the ERV (RTU intake)
° F
Air Temperature leaving the ERV (exhaust)
inH
O
Current building pressure
2
%
Current ERV wheel speed
%
Current ERV's intake fan speed
%
Current ERV's exhaust fan speed
%
ERV's SCR heater commanded capacity
ERV's motor failure alarm status
ERV's low CFM alarm status
ERV's General Alarm status
12