Target national account system factory installed energy recovery 48/50hc weathermasterr commercial rooftop units 12.5 nominal ton units with puron r-410a refrigerant and i/o flex 6126 controls (60 pages)
TABLE OF CONTENTS Section ................Page SAFETY SUMMARY .
Page 4
TABLE OF CONTENTS - - Continued: PUMPING THE SYSTEM DOWN OR REMOVING THE REFRIGERANT CHARGE ..4--3 4.4.1 System Pump Down For Low Side Repair ........4--3 4.4.2 Refrigerant Removal From An Inoperative Compressor.
Page 5
LIST OF ILLUSTRATIONS Figure ................. Page Figure 1--1 Coach Cutaway View .
SAFETY SUMMARY GENERAL SAFETY NOTICES The following general safety notices supplement the specific warnings and cautions appearing elsewhere in this manual. They are recommended precautions that must be understood and applied during operation and maintenance of the equipment covered herein. The general safety notices are presented in the following three sections labeled: First Aid, Operating Precautions and Maintenance Precautions.
Page 7
SAFETY SUMMARY SPECIFIC WARNINGS AND CAUTIONS WARNING Be sure to observe warnings listed in the safety summary in the front of this manual before perform- ing maintenance on the hvac system WARNING Read the entire procedure before beginning work. Park the coach on a level surface, with parking brake applied.
Instructions and Electrical Data for the Model DC12175 1.1.2 Condensing Section and DC12174 Air Conditioning equipment furnished by Carrier Transport Air Conditioning as shown in The condensing section includes the condenser coil (s) Table 1--1. Additional support manuals are referenced fan and motor assemblies, filter--drier, receiver (with in Table 1--2.
SYSTEM OPERATING CONTROLS AND 2 Manual Switches COMPONENTS A/C Mode Switch (ACMS) 1 Electronic Thermostat (TH) The drivers control is equipped with a single The system is equipped with an electronic HIGH--OFF--LOW switch. The switch is placed in the thermostat which operates in combination with a desired fan speed postion to start temperature control.
SOCKET Figure 1- -3 Relay Board REFRIGERANT SYSTEM COMPONENT NOTE SPECIFICATIONS Refer to 05g or 05K Operation and Service manuals for additional technical data, including a. Refrigeration Charge approved oils and oil capacity. Approximate R134a refrigerant charge will be be- d.
SAFETY DEVICES The system circuits are protected independently against high current draw with fuses F2 & F4 through System components are protected from damage F14 and vehicle main power fuse. Refer to the caused by unsafe operating conditions with safety schematic diagram in Section 5 for fuse locations.
Heat transfer is established caused by unsafe operating conditions with safety from the refrigerant (inside the tubes) to the condenser devices. Safety devices with Carrier Transicold supplied air (flowing over the tubes). The condenser tubes have equipment include high pressure switch (HPS), low fins designed to improve the transfer of heat from the pressure switch (LPS), circuit breakers and fuses.
SECTION 2 OPERATION 2.1 STARTING ANDSTOPPING INSTRUCTIONS Rising Temperature 2.1.1 Starting 5°F Above Fully Loaded Coil a. Start the vehicle engine. The evaporator (interior) 5°F Setpoint fans will start as soon as power is available from the vehicle electrical system. 4°F b.
a. Temperature Control 2.4 SEQUENCE OF OPERATION The unloaders are operaed as follows for temperature Operation begins when the A/C mode switch (ACMS) is control: placed in the HIGH or LOW position. This provides: 1 Compressor Unloader UV1. When return air temper- a signal the vehicle to apply 24V power from the ature falls to less than 2°F (1.1°C) above set point vechcle alternator to the ALT+ terminal (Refer to wiring...
Page 18
Once the temperature approaches set point, the unloading. thermostat will call for the system to unload. With the If either HPS or LPS open, relay FR is de--energized. thermostat calling for unloading, unloader valve UV1 is De--energizing FR opens a set of contacts to energized.
SECTION 3 TROUBLESHOOTING Table 3-1 General System Troubleshooting Procedures INDICATION/ REFERENCE POSSIBLE CAUSES TROUBLE SECTION System Will Not Cool Compressor will not run V-Belt loose or defective Check Clutch coil defective Check/Replace Clutch malfunction Check/Replace Compressor malfunction See Table 1--2 Electrical malfunction Coach power source defective Check/Repair...
Table 3-1 General System Troubleshooting Procedures - Continued INDICATION/ REFERENCE POSSIBLE CAUSES TROUBLE SECTION Abnormal Noise Or Vibrations - Continued Condenser or evaporator fans Loose mounting hardware Check/Tighten Defective bearings Replace Blade interference Check Blade missing or broken Check/Replace Control System Malfunction Will not control Sensor or Relay(s) defective Check...
To avoid damage to the earth’s ozone layer, use a refrigerant recovery system whenever removing refriger- ant. The refrigerant recovery system is available from Carrier Transicold (Carrier Transicold P/N MVSll--115 or MVSll--240). When working with refrigerants you must comply with all local government environmental laws.
The manifold gauge/hose set is available from Carrier Transicold. (Carrier Transicold P/N TO DISCHARGE OR VALVE STEM CAP 07-00294-00, which includes items 1 through 6, FROM SUCTION LINE Figure 4--3).
Close off pump valve, isolate vacuum gauge and stop pump. Wait 5 minutes to verify that vacuum holds. The vacuum pump is available from Carrier Transicold (Carrier Transicold P/N 07--00176--11). i. Recharge low side with R-134a to 20 to 30 PSIG by admitting vapor from the refrigerant cylinder.
g. Once vacuum is maintained, re-connect low pressure c. Add sufficient nitrogen to raise system pressure to switch. Backseat compressor service valves and dis- 150 to 200 psig (10.21 to 13.61 bar). connect manifold gauge set. d. Check for leaks. The recommended procedure for finding leaks in a system is with an electronic leak de- h.
f. Break the vacuum with nitrogen. Raise system pres- sure to approximately 2 psig. g. Purge the nitrogen from the system. h. Repeat steps d. thru g. one time. i. Start vacuum pump and open all valves. Dehydrate unit to 500 microns Hg vacuum. j.
4.7 ADDING REFRIGERANT TO SYSTEM c. Run the unit in the cool mode as described in section 4.7.1. With the suction service valve midseated, open 4.7.1 Checking Refrigerant Charge the refrigerant cylinder valve and add vapor charge until the refrigerant level appears in the liquid line The following conditions must be met to accurately sight glass.
d. Remove coil retaining clip and nameplate. WARNING e. Lift burned-out coil from enclosing tube and replace. f. Connect wire leads and test operation The filter-drier may contain liquid refriger- 4.12.2 Internal Part Replacement ant. Slowly loosen the flare nuts to avoid re- frigerant contact with exposed skin or eyes.
4.13.2 Superheat Measurement NOTE All readings must be taken from the TXV bulb location and out of the direct air stream. 1. Suction Line 4. Thermocouple (section view) 5. TXV Bulb (Shown 2. TXV Bulb Clamp in the 4’clock 1. Power Head 4.
filter will restrict air flow over the evaporator coil which may cause insufficient cooling or heating and possible frost buildup on the coil. To remove the filters, do the following. a. Place main battery disconnect switch in OFF position and lock. b.
ate compressor to 500 microns. Front seat both man- the same orientation as it was mounted on the original ifold valves to isolate the pump. compressor. Tighten the mounting bolts to 45-50 ft/ lbs (5.53-6.92 mkg). m.Open compressor service valves. n.
has been de--energized and the compressor is now in WARNING 4 cylinder operation. i. Continue to slowly back--seat the suction service Extreme care must be taken to ensure that valve and watch the suction gauge. When the suction pressure gauge “jumps” (3 to 5 psi-- 0.2 to 0.4 bar) all the refrigerant has been removed from note the pressure at which the gauge jumped in the the compressor crankcase or the resultant...
4.17 REPLACING SENSORS Pressure switches UPS1 and UPS2 are installed in the suction return line to the compressor. Each switch a. Place main battery disconnect switch in OFF position monitors suction pressure and operates one unloader and lock. by controlling the voltage applied to the unloader coil. b.
SECTION 5 ELECTRICAL 5- -1 INTRODUCTION This section contains electrical wiring schematics covering the models listed in Table 1--1. The schematics shown in this section provides information for all system models and optional configurations. The EM--17 evaporators are fitted with 2 blower/motor assemblies. The CM--5 Skirt--Mounted Condenser has 5 fan/motor assemblies and the KR--4 Rooftop Condenser has 4 fan/motor assemblies.