Other Applicable Documents - Viking VK1001 SR Upright Sprinkler K5.6 Technical Data Sheet

Table of Contents

Advertisement

1. PRODUCT IDENTIFICATION
This document covers the following product, hereafter referred to as "sprinkler"
(SR=Standard Response, QR=Quick Response):
VK1001 SR Upright Sprinkler K5.6 (80.6)
VK2001 SR Upright Sprinkler K8.0 (115)
VK2002 SR Upright Sprinkler K8.0 (115)
VK3001 QR Upright Sprinkler K5.6 (80.6)
VK3501 QR Upright Sprinkler K8.0 (115)
VK3502 QR Upright Sprinkler K8.0 (115)
VK1021 SR Pendent Sprinkler K5.6 (80.6)
VK2021 SR Pendent Sprinkler K8.0 (115)
VK2022 SR Pendent Sprinkler K8.0 (115)
!
WARNING
Cancer and Reproductive Harm www.P65Warning.ca.gov

2. OTHER APPLICABLE DOCUMENTS

For intended use and relevant conditions for the safe use of the specific sprinkler, refer to the appropriate Technical
Data Sheet. In case an installed sprinkler needs to be replaced, refer to the appropriate Handling and Installation
Instructions for the installation of the new sprinkler.
3. MAINTAINING OPERATIONAL READINESS
Functionality
During fire conditions, the operating element fuses or shatters (depending on the type of sprinkler), releasing the pip
cap and sealing assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform
spray pattern to control or extinguish the fire.
!
WARNING
This section contains important safety information. Read and follow all information.
Damaged or Compromised Sprinklers
Damaged or compromised sprinklers will not operate properly which could lead to loss of life.
NEVER clean, paint, or caulk sprinklers.
NEVER apply soap, water, ammonia, adhesives, solvents or any other fluids on sprinklers.
NEVER expose sprinklers to temperatures exceeding the maximum allowed ambient ceiling temperature. See the
Technical Data Sheet.
ALWAYS replace a compromised or damaged sprinkler.
NEVER attempt to repair or reassemble a sprinkler.
ALWAYS replace operated sprinklers and cover assemblies and sprinklers exposed to corrosive products of
combustion.
Replacement of sprinklers must only be performed following the instructions in section 4.
The following are examples in which sprinklers are considered damaged or compromised. Replace the sprinkler in the
following cases:
Sprinkler with a loss of fluid from the glass bulb or damage to the fusible element.
Sprinklers or cover plate assemblies that have been field painted, caulked, or mechanically damaged.
Sprinklers showing signs of extraordinary corrosion.
F_031022 Rev 01 August 25, 2022
Operation and Maintenance
Operation and Maintenance
Instructions
Instructions
Model XT-1 Sprinklers
VK3021 QR Pendent Sprinkler K5.6 (80.6)
VK3521 QR Pendent Sprinkler K8.0 (115)
VK3522 QR Pendent Sprinkler K8.0 (115)
VK1181 SR Conventional Sprinkler K5.6 (80.6)
VK1201 SR Conventional Sprinkler K8.0 (115)
VK1202 SR Conventional Sprinkler K8.0 (115)
VK3101 QR Conventional Sprinkler K5.6 (80.6)
VK3541 QR Conventional Sprinkler K8.0 (115)
VK3542 QR Conventional Sprinkler K8.0 (115)