1. DESCRIPTION
Viking Standard Response Fusible Link Upright Sprinkler VK108 is a small thermosensitive
solder link spray sprinkler available with various finishes and temperature ratings to meet
design requirements. The special Polyester and Electroless Nickel PTFE (ENT) coatings can
be used in decorative applications where colors are desired. In addition, these coatings have
been investigated for installation in corrosive environments and are listed/approved as indi-
cated in the Approval Chart(s).
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approved: Classes 2016 and 2017
Refer to the Approval Charts and Design Criterion for Listing/Approval requirements that must
be followed.
3. TECHNICAL DATA
Specifications:
Minimum Operating Pressure: 7 psi (0.5 bar)
Maximum Working Pressure: 175 psi (12 bar) wwp
Factory tested hydrostatically to 500 psi (34.5 bar)
Thread size: 1/2" (15 mm) NPT
Nominal K-factor: 5.6 U.S. (80.6 metric**)
Overall Length: 2-1/4" (58 mm)
** Metric K-factor measurement shown is in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
Material Standards:
Frame Casting: Brass UNS-C84400
Deflector: Brass UNS-C23000 or Copper UNS-C19500
Fusible Link Assembly: Brass UNS-C40500 and UNS-C51000
NOTE: For chrome sprinklers, the fusible link assembly is painted silver for decorative purposes only.
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Screw: Brass UNS-C36000
Seat: Copper UNS-C11000
Pip Cap Attachement: UNS-C36000
For Polyester Coated Sprinklers: Belleville Spring-Exposed
For ENT Coated Sprinklers: Belleville Spring-Exposed, Screw and Pip Cap-ENT Coated
Ordering Information: (Also refer to the current Viking price list.)
Viking Standard Response Fusible Link Upright Sprinkler VK108 by first adding the appropriate suffix for the sprinkler finish and
then the appropriate suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, Wax Coated = C, and ENT = JN
Temperature Suffix: 165 °F (74 °C) = C, 220 °F (104 °C) = F, 286 °F (141 °C) = G
For example, sprinkler VK108 with a 1/2" thread, Brass finish and a 165 °F (74 °C) temperature rating = Part No. 12973AC
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the Viking website.)
Sprinkler Wrenches:
A. Standard Wrench: Part No. 21475M/B (available since 2017).
B. Standard Wrench for Wax Coated Sprinklers: Part No. 10896W/B (available since 2000)
Sprinkler Cabinets:
A. Six-head capacity: Part No. 01724A (available since 1971)
B. Twelve-head capacity: Part No. 01725A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
Form No. F_052214
21.09.29
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Rev 21.1
STANDARD RESPONSE
FUSIBLE LINK UPRIGHT
SPRINKLER VK108 (K5.6)
Replaces Form No. F_052214 Rev 19.2
(Removed Cap render in Figure 1.)
Page 1 of 5

Advertisement

loading

Summary of Contents for Viking VK108

  • Page 1 Temperature Suffix: 165 °F (74 °C) = C, 220 °F (104 °C) = F, 286 °F (141 °C) = G For example, sprinkler VK108 with a 1/2” thread, Brass finish and a 165 °F (74 °C) temperature rating = Part No. 12973AC Available Finishes And Temperature Ratings: Refer to Table 1.
  • Page 2: Technical Data

    Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY The Viking Standard Response Fusible Link Upright Sprinkler VK108 is available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
  • Page 3 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES...
  • Page 4 (Also refer to Approval Chart 1.) cULus Listing Requirements: Viking Standard Response Fusible Link Upright Sprinkler VK108 is cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers.
  • Page 5 FM Approval Requirements: Sprinkler VK108 is FM Approved as a standard response Non-Storage upright sprinkler as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
  • Page 6 Refer to the appropriate technical data page and NFPA standards for complete care, handling, installation, and maintenance instructions. For additional product and system information Viking data pages and installation instructions are available on the Viking Web site at www.vikinggroupinc.com.
  • Page 7 * Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www. vikinggroupinc.com.
  • Page 8 • while ceiling finish work is being completed. Use only the designated Viking recessed sprinkler wrench (refer to the appropriate sprinkler data page) to install these sprinklers. NOTE: The protective cap is • temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed.
  • Page 9 Take care not to crack the wax coating on the units. • For touching up the wax coating after installation, wax is available from Viking in bar form. Refer to Table 1 below. The coating MUST be repaired after •...
  • Page 10: Warranty Terms And Conditions

    For more information, go to www.P65Warnings.ca.gov 2. WARRANTY TERMS AND CONDITIONS For details of warranty, refer to Viking’s current list price schedule at www.vikinggroupinc.com or contact Viking directly. New Bulletin Form No. F_111218 18.11.15...