Viking VK1202 Technical Data Manual

Viking VK1202 Technical Data Manual

Standard response conventional sprinkler (k8.0)

Advertisement

Quick Links

Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
1. DESCRIPTION
The Viking VK1202 Standard Response Conventional Sprinklers are small,
thermosensitive, glass-bulb spray sprinklers available in several different finishes,
temperature ratings, and K-factors to meet design requirements. The special Polyester,
and Electroless Nickel Polytetrafluoroethylene (ENT), coatings can be used in decorative
applications where colors are desired. In addition, these coatings have been investigated
for installation in corrosive environments and are listed as indicated in the Approval
Chart.
Standard Response sprinklers may be ordered and/or used as open sprinklers
(glass bulb and pip cap assembly removed) on deluge systems. Refer to Ordering
Information.
2. LISTINGS AND APPROVALS*
cULus Listed: Category VNIV
LPCB Approved reference no. 096m
* Not approved for new installations per NFPA 13. Refer to the Approval Chart and Design
Criteria for Listing requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Minimum Operating Pressure: 7 psi (0.5 bar)
Rated to: 175 PSI (12 bar)
Factory tested hydrostatically to 500 psi (34.5 bar).
Thread size: 1/2" NPT or 15 mm BSPT
Nominal K-factor: 8.0 U.S. (115 metric**)
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
** Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
Material Standards:
Sprinkler Body: Brass CW602N, UNS-C84400 or QM Brass
Deflector: Stainless Steel UNS S30400
Pip Cap Shell - Stainless Steel UNS-S44400
Pip Cap Disc - Stainless Steel UNS-S30100
Belleville Spring - Nickel Alloy
Pip Cap Seal - Polytetrafluoroethylene (PTFE)
Compression Screw: Brass CW612N, CW508L, UNS-C36000 or UNS-C26000
Shipping Cap: Polyethylene
Bulb: Glass, nominal 5 mm diameter
Ordering Information: (Refer to Table 1.)
4. INSTALLATION
Refer to appropriate NFPA and/or any other applicable installation standards.
NOTICE
Risk of permanent damage.
Over-tightening the sprinkler can cause permanent damage.
> Tighten the sprinkler to a MAXIMUM torque of 14 ft-lbs. (19.0 N-m).
5. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
6. INSPECTIONS, TESTS, AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
The Model VK1202 Sprinkler is available through a network of domestic and international distributors. See the web site for the
closest distributor or contact Viking.
8. GUARANTEE
For details of warranty, refer to the current list price schedule or contact us directly.
Form No. F_102718 Rev 22.1
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
March 3, 2022
VK1202 STANDARD
RESPONSE CONVENTIONAL
SPRINKLER (K8.0)
Replaces Form No. F_102718 Rev 21.1
(Added LPCB details, removed CE.)
Page 1 of 3

Advertisement

Table of Contents
loading

Summary of Contents for Viking VK1202

  • Page 1 6. INSPECTIONS, TESTS, AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY The Model VK1202 Sprinkler is available through a network of domestic and international distributors. See the web site for the closest distributor or contact Viking. 8. GUARANTEE For details of warranty, refer to the current list price schedule or contact us directly.
  • Page 2: Technical Data

    OPEN Example: 22102MBW = VK1202 with White Polyester Finish and 155 °F (68 °C) Nominal temperature rating. This sprinkler is to be installed into an area with a maximum ambient temperature of 100 °F (38 °C) meaning if the area will experience temperatures above the maximum ambient rating, you shall use a higher temperature-rated sprinkler.
  • Page 3 DESIGN CRITERIA - UL cULus Listing Requirements: The Viking Standard Response Conventional Sprinkler VK1202 is cULus Listed as indicated in the Approval Chart for installation in accordance with the latest edition of NFPA 13 for old style (conventional) sprinklers. • Designed for use in Light, Ordinary, and Extra Hazard occupancies.
  • Page 4 Refer to the appropriate technical data page and NFPA standards for complete care, handling, installation, and maintenance instructions. For additional product and system information Viking data pages and installation instructions are available on the Viking Web site at www.vikinggroupinc.com.
  • Page 5 * Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www. vikinggroupinc.com.
  • Page 6 • while ceiling finish work is being completed. Use only the designated Viking recessed sprinkler wrench (refer to the appropriate sprinkler data page) to install these sprinklers. NOTE: The protective cap is • temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed.
  • Page 7 Take care not to crack the wax coating on the units. • For touching up the wax coating after installation, wax is available from Viking in bar form. Refer to Table 1 below. The coating MUST be repaired after •...
  • Page 8: Listings And Approvals

    1. DESCRIPTION Viking fire sprinklers consist of a threaded frame with a specific waterway or orifice size and a deflector for distributing water in a specified pattern. A closed or sealed sprinkler refers to a complete assembly, including the thermosensitive operating element. An open sprinkler does not use an operating element and is open at all times.
  • Page 9 TECHNICAL DATA SPRINKLER OVERVIEW The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com VERTICAL SIDEWALL (VSW) SPRINKLER: A sprinkler intended for installation near the wall and ceiling. The deflector provides a water spray pattern outward in a quarter-spherical pattern and can be installed in the upright or pendent position with the flow arrow in the direction of discharge.
  • Page 10 Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
  • Page 11: Installation

    STANDARD RESPONSE, QUICK RESPONSE, EXTENDED COVERAGE, AND DRY SPRINKLERS Viking thermosensitive spray sprinklers consist of a small frame and either a glass bulb or a fusible operating element. Available styles include pendent, flush pendent, concealed pendent, upright, horizontal sidewall, vertical sidewall, or conventional, depending on the particular sprinkler model selected.
  • Page 12 C. Installation Instructions - Dry Sprinklers WARNING: Viking dry sprinklers are to be installed in the 1” outlet (for dry and preaction systems), or run of malleable, ductile iron, or Nibco CPVC* threaded tee fittings (for wet systems) that meet the dimensional requirements of ANSI B16.3 (Class 150), or cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16.4 (Class 125), even at branch line ends.
  • Page 13: Operation

    4. After installation, the entire sprinkler system must be tested. The test must be conducted to comply with the installation stand- ards. Viking high pressure sprinklers may be hydrostatically tested at a maximum of 300 psi (20.7 bar) for limited periods of time (two hours), for the purpose of acceptance by the Authority Having Jurisdiction.
  • Page 14 Refer to the Authority Having Jurisdiction for minimum replacement requirements. 7. AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
  • Page 15: Warranty Terms And Conditions

    For more information, go to www.P65Warnings.ca.gov 2. WARRANTY TERMS AND CONDITIONS For details of warranty, refer to Viking’s current list price schedule at www.vikinggroupinc.com or contact Viking directly. New Bulletin Form No. F_111218 18.11.15...
  • Page 16: General Information

    Model XT1 Sprinklers; no other guard assemblies should be used. WARNING Viking sprinklers are manufactured and tested to meet the rigid requirements of the approving agency. The sprinklers are designed to be installed in accordance with recognized installation standards. Deviation from the standards or...

Table of Contents