Siemens SIMATIC NET RUGGEDCOM RS930L Installation Manual page 43

Hide thumbs Also See for SIMATIC NET RUGGEDCOM RS930L:
Table of Contents

Advertisement

Certification
6.2 EMC and Environmental Type Tests
61000-4-17
61000-4-29
60255-27
EMC Immunity Type Tests per IEEE 1613
Note
RUGGEDCOM products meet Class 1 requirements for copper Ethernet
configurations and Class 2 for fiber Ethernet configurations. Class 1 allows for
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
Fast Transient
Dielectric Strength
34
Test
IEC
Ripple on DC Power Supply
IEC
Voltage Dips and Interrupts
IEC
Dielectric Strength
HV Impulse
Description
ESD
Radiated RFI
Oscillatory
HV Impulse
Description
DC Power
Ports
DC Power
Ports
DC Power
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
Test Levels
30 V Continuous
300 V for 1 s
15%
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
2 kV (Failsafe Relay Output)
2 kV
2 kV
5 kV (Failsafe Relay Output)
5 kV
5 kV
Test Levels
± 8 kV
± 15 kV
35 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV
± 4 kV
2.5 kV Common Mode @ 1 MHz
2.5 kV Common and
Differential Mode @ 1 MHz
2.5 kV Common and
Differential Mode @ 1 MHz
5 kV (Failsafe Relay)
5 kV
5 kV
2 kV (Failsafe Relay)
Installation Manual, 11/2022, C79000-G8976-1034-11
Severity
Levels
4
3
 
 
 
 
 
 
 
RUGGEDCOM RS930L

Advertisement

Table of Contents
loading

Table of Contents