Fujitsu AU G18LVLB Series Design & Technical Manual page 188

1 phase type simultaneous multi system
Hide thumbs Also See for AU G18LVLB Series:
Table of Contents

Advertisement

(7) To return to "Operating status display (Normal operation)", press the EXIT switch button (SW4).
In case of missing how many times you pressed the SELECT and ENTER switch buttons:
1. To return to "Operation status display (Normal operation)", press the EXIT switch button
once.
2. Restart from the beginning of setting procedure.
NOTE: In case of missing how many times you pressed the SELECT and ENTER switch buttons,
you must redo the setting procedure. Return to "Operation status display (Normal operation)" by
pressing the EXIT switch button once, and restart from the beginning of the setting procedure.
PEAK CUT MODE
LED lamp part
SW1
SW2
(1) Press the MODE switch button (SW1) for 3 seconds or more to switch to "Local setting mode".
(2) After confirming the LED lamp of POWER/MODE blinks 9 times, press the ENTER switch
button (SW3).
PUMP
POWER
LOW NOISE
ERROR
DOWN
MODE
(L1)
(L2)
Blinks
(9 times)
Sign "
" : Lights off
(3) Press the SELECT switch button (SW2), and adjust the LED lamp as shown below. Then the
LED lamp indicates the current setting.
LOW NOISE
(L2)
PEAK CUT
Blink
MODE
(4) Press the ENTER switch button (SW3).
LOW NOISE
(L2)
PEAK CUT
MODE
Sign "
(5) Press the SELECT switch button (SW2), and adjust the LED lamps as shown below.
100% of rated input ratio
75% of rated input ratio
50% of rated input ratio
0% of rated input ratio
SW3
SW4
SW5
PEAK CUT
(L3)
(L4)
(L5)
(L6)
(L3)
(L3)
" : Lights on
PEAK CUT
(L4)
(L5)
(L6)
Blink
Blink
Blink Blink
Blink
- (04-46) -

Advertisement

Table of Contents
loading

Table of Contents