External Input And Output; Outdoor Unit; External Input - Fujitsu AU G18LVLB Series Design & Technical Manual

1 phase type simultaneous multi system
Hide thumbs Also See for AU G18LVLB Series:
Table of Contents

Advertisement

5.

EXTERNAL INPUT AND OUTPUT

5-1.

OUTDOOR UNIT

With using external input and output functions, this product can be operated inter-connectedly with
an external device.
Connector
CN10
CN11
CN12
CN13
5-1-1.

EXTERNAL INPUT

With using external input function, on/off status of "Low noise mode" and "Peak cut mode" can be
specified by the external signal.
LOW NOISE MODE
In following condition, the operating noise of the outdoor unit reduces comparing from the one in
normal operating condition:
The air conditioner is set to the "Low noise mode" when closing the contact input of a commercial
timer or on/off switch to a connector on the control PCB of the outdoor unit.
NOTE: Product performance may drop depending on some conditions such as the outdoor
temperature.
Circuit diagram example
z
Outdoor unit
control PCB
Connector
1
2
Input Signal
Low noise mode
Optional part
z
Parts name
External connect kit
Input
Low noise mode
Peak cut mode
Connected unit
Ex.) Switch
*10m
Signal
Locally purchased
ON
OFF
ON
OFF
Model name
UTY-XWZXZ3
Output
Error status
Compressor status
Contact capacity: DC 24 V or more, 10 mA
or more.
*: Make the distance from the PCB to the
connected unit within 10 m.
Construct a circuit as shown in this figure
with using optional parts mentioned below.
Input signal: On in "Low noise mode"
Input signal: Off in normal operation
To set the level of "Low noise mode", refer
to "Low noise mode" in 6.FUNCTION
SETTINGS.
Exterior
- (04-33) -
Remarks
See external input/output
settings for details.

Advertisement