Fujitsu AU G18LVLB Series Design & Technical Manual page 176

1 phase type simultaneous multi system
Hide thumbs Also See for AU G18LVLB Series:
Table of Contents

Advertisement

PEAK CUT MODE
By performing following on-site work, operation that suppresses the current value can be enabled:
The air conditioner is set to the "Peak cut mode" when closing the contact input of a commercial
timer or on/off switch to a connector on the control PCB of the outdoor unit.
Circuit diagram example
z
Outdoor unit
control PCB
Connector
1
2
Input Signal
Peak cut mode
Optional part
z
Parts name
External connect kit
Connected unit
Ex.) Switch
*10m
Signal
Locally purchased
ON
OFF
ON
OFF
Model name
UTY-XWZXZ3
.Contact capacity: DC 24 V or more, 10 mA
or more.
*: Make the distance from the PCB to the
connected unit within 10 m.
Construct a circuit as shown in this figure
with using optional parts mentioned below.
Input signal: On in "Peak cut mode"
Input signal: Off in normal operation
To set the level of "Peak cut mode", refer
to "Peak cut mode" in 6.FUNCTION
SETTINGS.
Exterior
- (04-34) -