Coil Cleaning; Refrigerant Coils; Steam Or Hot Water Coils - Trane IntelliPak 2 Installation, Operation And Maintenance Manual

Commercial rooftop air conditioners
Table of Contents

Advertisement

Service and Maintenance
WARNING
Hazardous Gases and Flammable
Vapors!
Failure to observe the following instructions could
result in exposure to hazardous gases, fuel
substances, or substances from incomplete
combustion, which could result in death or
serious injury. The state of California has
determined that these substances may cause
cancer, birth defects, or other reproductive harm.
Improper installation, adjustment, alteration,
service or use of this product could cause
flammable mixtures or lead to excessive carbon
monoxide. To avoid hazardous gases and
flammable vapors follow proper installation and
setup of this product and all warnings as provided
in this manual.
☐ Verify that the ignition system operates properly.

Coil Cleaning

Regular coil maintenance, including annual cleaning
enhances the unit's operating efficiency by minimizing the
following:
Compressor head pressure and amperage draw
Water carryover
Fan brake horsepower
Static pressure losses
At least once each year—or more often if the unit is located
in a "dirty" environment—clean the evaporator,
microchannel condenser, and reheat coils using the
instructions outlined below. Be sure to follow these
instructions as closely as possible to avoid damaging the
coils.
WARNING
Hazardous Chemicals!
Failure to follow this safety precaution could result in
death or serious injury. Coil cleaning agents can be
either acidic or highly alkaline and can burn severely
if contact with skin or eyes occurs.
Handle chemical carefully and avoid contact with
skin. ALWAYS wear Personal Protective Equipment
(PPE) including goggles or face shield, chemical
resistant gloves, boots, apron or suit as required. For
personal safety refer to the cleaning agent
manufacturer's Materials Safety Data Sheet and follow
all recommended safe handling practices.

Refrigerant Coils

To clean refrigerant coils, use a soft brush and a sprayer.
Important: DO NOT use any detergents with microchannel
condenser coils. Pressurized water or air
ONLY.
186
For evaporator and reheat coil cleaners, contact the local
Trane Parts Center for appropriate detergents.
1. Remove enough panels from the unit to gain safe
access to coils.
2. Straighten any bent coil fins with a fin comb.
3. For accessible areas, remove loose dirt and debris
from both sides of the coil. For dual row microchannel
condenser coil applications, seek pressure coil wand
extension through the local Trane Parts Center.
4. When cleaning evaporator and reheat coils, mix the
detergent with water according to the manufacturer's
instructions. If desired, heat the solution to 150° F
maximum to improve its cleansing capability.
Important: DO NOT use any detergents with
microchannel coils. Pressurized water or
air ONLY.
5. Pour the cleaning solution into the sprayer. If a high-
pressure sprayer is used:
a. The minimum nozzle spray angle is 15 degrees.
b. Do not allow sprayer pressure to exceed 600 psi.
c. Spray the solution perpendicular (at 90 degrees) to
the coil face.
d. For evaporator and reheat coils, maintain a
minimum clearance of 6" between the sprayer
nozzle and the coil. For microchannel condenser
coils, optimum clearance between the sprayer
nozzle and the microchannel coil is 1"-3".
6. Spray the leaving-airflow side of the coil first; then
spray the opposite side of the coil. For evaporator and
reheat coils, allow the cleaning solution to stand on the
coil for five minutes.
7. Rinse both sides of the coil with cool, clean water.
8. Inspect both sides of the coil; if it still appears to be
dirty, repeat Steps 6 and 7.
9. Reinstall all of the components and panels removed in
Step 1; then restore power to the unit.
10. For evaporator and reheat coils, use a fin comb to
straighten any coil fins which were inadvertently bent
during the cleaning process.

Steam or Hot Water Coils

To clean a steam or hot water coil, use a soft brush, a
steam-cleaning machine, and water.
1. Verify that switches 1S1 and 1S70 are turned "OFF",
and that the main unit disconnect is locked open.
WARNING
No Step Surface!
Failure to follow instruction below could result in
death or serious injury.
Do not walk on the sheet metal drain pan. Walking on
the drain pan could cause the supporting metal to
collapse and result in the operator/technician falling.