Trane IntelliPak 2 Installation, Operation And Maintenance Manual page 181

Commercial rooftop air conditioners
Table of Contents

Advertisement

Table 78. Supply fan VDF programming parameters (continued)
Menu
4-12
4-14
Limits/warnings
4-18
4-19
5-10
Digital in/out
5-12
5-13
8-30
8-31
8-32
8-33
Communications and
8-35
Options
8-36
8-01
8-03
8-04
14-01
14-11
14-12
Special Function
14-20
14-50
14-61
22-60
22-61
Application Function
22-62
RT-SVX073A-EN
Description
ID
Motor Speed Low Limit [HZ]
Motor Speed High Limit (Hz)
Current Limit (%)
Max Output Frequency (HZ)
Terminal 18 Digital Input
Terminal 27 Digital Input
Terminal 29 Digital Input
Protocol
Address
Baud Rate
Parity / Stop Bits
Minimum Response Delay (s)
Maximum Response Delay (s)
Control Site
Control Timeout Time (s)
Control Timeout Function
Switching Frequency (kHz)
Mains Voltage Fault level
Function at Main Imbalance
Reset Mode
RFI Filter
Function at Inverter Overload
Broken Belt Function
Broken Belt Torque (%)
Broken Belt Delay (s)
Parameter Setting
[22] 22 Hz
[50] 50 Hz - 380/50Hz Supply Only [60] 60 Hz
[100] 100%
[50] 50 Hz - 380/50Hz Supply Only [60] 60 Hz
[0] No Operation
[0] No Operation
[0] No Operation
[2] Modbus RTU
[7] For SUPPLY FAN 4M12
[7] 115200 Baud
[0] Even Parity, 1 Stop Bits
[0.005] 5ms Min Response Delay Time
[0.1] 100ms Max Response Delay Time
[2] Controlword onlly
[15] 15s
[2] Stop
[5] 5.0 KHz
Set based on motor nameplate voltage [177] for 208V motor [196] for 230V
motor [323] for 380V motor [353] for 415V motor [391] for 460V motor [489] for
575V motor
[3] Derate
[5] Automatic reset x 5
[0] Off
[1] Derate
[2] Trip
[10] 10%
[60] 60 Seconds
Service and Maintenance
181