Samsung AM CXV Series Installation Manual page 48

Table of Contents

Advertisement

Setting outdoor unit option switch and key function
Optional item
Silent mode
High-head condition
setting
Long-piping
condition setting
Energy control
operation
Rotation defrost
(HR only)
Expand operational
temperature range
for cooling operation
(HR only)
Channel address
Snow accumulation
prevention control
Unused option
Unused option
48
English
DB68-11976A-00_IM_DVM S2 Outdoor_SA_EN_.indd 48
DB68-11976A-00_IM_DVM S2 Outdoor_SA_EN_.indd 48
Input unit
SEG1
SEG2
SEG3
0
0
0
0
0
Main
0
7
0
0
0
0
0
0
0
Main
0
8
0
0
0
0
Main
0
9
0
0
0
Main
1
0
0
0
Main
1
1
0
0
Main
1
2
0
A
Main
1
3
0 ~ 15
0
Main
1
4
0
Main
1
5
0
Main
1
6
0
SEG4
Function of the option
0
Disabled (Factory default)
1
LEVEL 1 / Auto
2
LEVEL 2 / Auto
3
LEVEL 3 / Auto
4
LEVEL 1 / External contact
5
LEVEL 2 / External contact
6
LEVEL 3 / External contact
7
LEVEL 1
8
LEVEL 2
9
LEVEL 3
0
Disabled (Factory default)
Level 1 of height difference type 1
1
(Indoor unit is lower than outdoor
unit)
Level 2 of height difference type 1
2
(Indoor unit is lower than outdoor
unit)
Height difference type 2 (Outdoor
3
unit is lower than indoor unit)
0
Disabled (Factory default)
1
LEVEL 1
2
LEVEL 2
0
Basic (Factory default)
1
Energy saving
2
Power
0
Disabled (Factory default)
1
Enabled
0
Disabled (Factory default)
1
Enabled
U
Automatic setting (Factory default)
Manual setting for channel 0~15
0
Enabled (Factory default)
1
Disabled
0
Unused option
0
Unused option
Remarks
Enables the silent mode for night-
time in cooling mode (It operates
automatically depending on the
temperature.)
However, if the external contact
interface module (MIM-B14) is used,
entering the silent mode is available
with contact signal in cooling and
heating mode.
When outdoor unit is located
40~80m above the indoor unit
When outdoor unit is located over
80m above the indoor unit
When indoor unit is over 30 m above
the outdoor unit
When equivalent length of farthest
indoor unit from the outdoor unit is
between 100~170m
When equivalent length of farthest
indoor unit from the outdoor unit is
over 170m
Energy control option of designated
operation sequence
Operating in energy saving mode,
capacity might decrease compared to
normal operation mode
When enabled, continuous heating
operation is possible but heating
performance will decrease during
rotation defrost operation
When enabled, continuous cooling
operation is possible even in low
temperature condition up to -15°C,
but noise of the MCU will increase
Address for classifying the product
from upper level controller (DMS,
S-NET 3, etc.)
During snow accumulation, the fan
may spin even when the unit is not
in operation
Unused option by this model
Unused option by this model
2022-09-13 오전 9:34:24
2022-09-13 오전 9:34:24

Advertisement

Table of Contents
loading

Table of Contents