Insulating the pipe located inside of the
outdoor unit
• With a pipe insulator, insulate the pipe up to whole service
valve located inside of the outdoor unit.
• Seal the gap between the outdoor unit pipe and the insulator.
Rainwater and dewdrops may soak through the gap between
the pipe and the insulation of the outdoor unit installed on the
outside.
• Separate the cover of the pipe and close it after insulation
work. Only remove a knock-out hole cover where the pipe
will be installed. If the knock-out hole is open unnecessarily,
it must be closed. If not, small animals such as squirrels and
rats may get into the unit through the hole and the unit may
be damaged.
H/P
CAUTION
• The filled-out label must be adhered in the proximity of the
product charging port.
(ex. onto the inside of the stop valve cover.)
DB68-11976A-00_IM_DVM S2 Outdoor_SA_EN_.indd 43
DB68-11976A-00_IM_DVM S2 Outdoor_SA_EN_.indd 43

Single installation

• Open the manifold gauge valve connected to the liquid side
service valve and add the liquid refrigerant.
• If you cannot add the whole quantity of the refrigerant while
the outdoor unit is stopped, open the gas side and liquid side
service valve. Then, add remaining refrigerant by pressing the
refrigerant adding button of the outdoor PCB.
Gas side
R-410A
(Inject
liquid
refrigerant)
Scale
Vacuum port

Module installation

• Open the manifold gauge valve connected to the liquid side
service valve and add the liquid refrigerant.
• If you cannot add the whole quantity of the refrigerant while
the outdoor unit is stopped, open the gas side and liquid side
service valve. Then, add remaining refrigerant by pressing the
refrigerant adding button of the outdoor PCB.
• If you use the refrigerant charging function from the PCB,
outdoor unit will operate and charge the refrigerant. At
this time, you must use gas side manifold gauge for cooling
operation and use charging port for heating at the manifold
gauge for heating operation.
Manifold gage
Gas
R-410A
side
(Inject
liquid
refrigerant)
Scale
Vacuum port
Outdoor unit
Liquid side
Manifold gage
Service valve
Outdoor unit
Outdoor unit
Liquid side
Liquid side
Service valve
pipe
43
English
2022-09-13 오전 9:34:22
2022-09-13 오전 9:34:22