Outdoor unit installation
CAUTION
• Cautions regarding on connecting the anchor bolt
– Tighten the rubber washer to prevent the bolt connection
part of the outdoor unit from corroding.
– Anchor specification
Diameter
Size
of drill
bit (a)
14mm
Ø 10
(1/2")
※ Use the anchor bolts and nuts that is zinc plated or made of
STS material. Regular anchor bolts or nuts may get damaged
by corrosion.
• Cautions regarding on connecting the pipe
– If you install the outdoor unit on the rooftop, check the
strength and make sure to waterproof the rooftop.
– Construct draining pit around the base construction and
pay attention to the drainage around the outdoor unit.
(Condensation or defrost water may form during outdoor
unit operation.)
– If there's any possibility of small animals from entering the
pipe outlet, block the outlet as shown in the illustration.
Block the
from the front side)
• Cautions regarding on anti-vibration frame installation
– During installation, make sure there is no gap between the
base ground and the supporting structures such as anti-
vibration frame or H beam.
– Base ground must be constructed strongly to support the
bottom part of the anti-vibration mount.
– After installing the anti-vibration frame, untighten the
fixing part on the top and bottom part of the frame.
14
English
DB68-11976A-00_IM_DVM S2 Outdoor_SA_EN_.indd 14
DB68-11976A-00_IM_DVM S2 Outdoor_SA_EN_.indd 14
Rubber washer
Anchor
Sleeve
Insert
Fastening
length (b)
length (c)
depth
torque
75mm
40mm
50mm
30 N·m
(3")
(1-1/2")
(2")
m
a
part. (When withdrawing the pipe
Liquid side pipe
Gas side pipe
• Caution for installing discharge duct
– Static pressure of the discharge duct should be within the
standard specification when installing the duct.
– If you remove the fan guard to install the discharge duct,
make sure to install a safety net on the duct outlet. Foreign
substance may enter into the product and there could be a
risk of personal injury.
– Wear protection equipment at all times when making
galvanized sheet metal duct, since the worker may get
injured by the sharp parts.
– When installing the outdoor unit under the tree or near
forest, leafs may get into the product and cause problems
on the product. Therefore, install a discharge duct to
prevent foreign substance infiltration.
<Preventing foreign substance infiltration>
Installing the outdoor unit in various
environments
Installing the outdoor unit around the obstacles
• It is necessary to install a discharge guide duct(field supply) to
direct exhaust from the fan horizontally, when it is difficult to
provide a minimum space of 2m (6.56ft) between the air outlet
and a nearby obstacle.
Upper floor
Ex.) Balcony
Discharged air
Grille/louver
Suction air
Ex.) Mechanical room
Discharged air