Safety Information
– When replacing/repairing the PCB, cut-off the power and
wait until the DC voltage is discharged before replacing/
repairing them. (Wait for more than 15 minutes to allow it
to discharge naturally.)
• If the refrigerant gas leaks during the installation, you should
ventilate the room.
– When the refrigerant gas gets in contact with flammable
substance, it may generate toxic gas.
• Gas leakage must be checked after installation is completed.
– When the refrigerant gas gets in contact with flammable
substance, it may generate toxic gas.
• You can get a frostbite if you get in contact with the leaked
refrigerant gas.
• Supply power to the product during winter time since the
product will operate in protection mode itself when the
temperature decrease below 0℃ (32℉).
– If you cut-off the power, compressor protection mode
cannot be operated and may cause damage to the product.
• Wear protective equipment (such as safety gloves, goggles,
and headgear) during installation and maintenance works.
Installation/repair technicians may be injured if protective
equipment is not properly equipped.
• This appliance is not intended for use by persons (including
children) with reduced physical, sensory or mental capabilities,
or lack of experience and knowledge, unless they have been
given supervision or instruction concerning use of the appliance
by a person responsible for their safety. Children should be
supervised to ensure that they do not play with the appliance.
For use in Europe : This appliance can be used by children aged
from 8 years and above and persons with reduced physical,
sensory or mental capabilities or lack of experience and
knowledge if they have been given supervision or instruction
concerning use of the appliance in a safe way and understand
the hazards involved. Children shall not play with the appliance.
Cleaning and user maintenance shall not be made by children
without supervision.
CAUTION
• Do not install the drain pipe directly to the bottom part of the
outdoor unit and built a proper drainage so that water drains
out smoothly. If not, pipe may freeze or bursts during winter
time and cause damage to the product or water leakage.
– When the draining work is not done properly, water leak
may occur and cause property damage.
• Install the power cable and communication cable of the indoor
and outdoor unit at least 1.5m (4.92ft) away from the electric
appliances and install it at least 2m (6.56ft) away from the
lightning conductor.
– Noise may be generated from the electronic devices,
depending on the status of the electric wave.
• Install the outdoor unit within the angle stated in the table,
according to the height of the building.
– Do not leave the refrigerant container under the hot
sunlight. (There is risk of explosion.)
– You must use the appropriate pipes according to the
standard since the pressure of the refrigerant is high.
– Make sure that the pipes does not get any weaker by
welding it too much.
– Make sure to install the product away from children's'
reach. (Sharp parts of the heat exchanger may cause
personal injury and when parts of the product gets
damage, it may decrease product's performance.)
4
English
DB68-11976A-00_IM_DVM S2 Outdoor_SA_EN_.indd 4
DB68-11976A-00_IM_DVM S2 Outdoor_SA_EN_.indd 4
Lightning rod
Protection angle: 25˚~55˚
Height of the building
20m(65.6 ft) or less
40m(131.2 ft) or less
60m(196.9 ft) or less
• Install the indoor unit away from lighting apparatus that uses
ballast stabilizer.
– If you use the wireless remote control, it may not operate
normally due to ballast stabilizer.
• Do not install the product in following places.
– Place where outdoor unit's noise and warm air may disturb
neighbors. (It may cause property loss.)
– Do not leave any obstacles around the inlet and outlet of
the product. (It may cause damage or accidents.)
– The place where there is mineral oil or arsenic acid.
– Those parts may get damaged due to burned resin and
cause water leakage or product may fall.
– The efficiency of the heat exchanger may reduce or
product may break.
– The place where corrosive gas such as sulfurous acid gas
generates from the vent pipe or air outlet.
– The copper pipe or connection pipe may corrode and
refrigerant may leak.
– The place where there is a machine that generates
electromagnetic waves.
– The air conditioner may not operate normally due to
problems in control system.
– The place where there is a danger of combustible gas
leakage or place where thinner or gasoline is handled.
– (There is risk of fire or explosion.)
– The place with carbon fiber or flammable dust.
– The place near seashore or hot spring where there is risk of
outdoor unit corrosion.
• Changes in DVM S2 (inverter) compare to conventional models
that has to noted when installing
– For optimal distribution of the refrigerant, you must use Y-joint
as branch joint for connecting outdoor units. (Do not use T-joint)
– You cannot operate normally if you do not complete the
trial operation through outdoor unit key mode. You must
use KEY MODE to run trial operation.
– Check the compatibility of other products such as indoor
unit, EEV kits etc. which will be connected to DVM S2.
– Make sure to note that outdoor unit combination is
different from DVM PLUS III, IV and DVM S.
– The length of maximum piping, level difference, the
quantity of connectable indoor units, the installation at
the outdoor joints and the outdoor unit combinations are
different from the conventional models.
– If the pipe length is over 2m (6.56ft) between outdoor units,
make traps to prevent oil stagnation. Oil stagnation may
occur when outdoor unit at the end of module stops while
other outdoor units are still in operation.
Protection angle
55˚
35˚
25˚