Flame Sensor - Lennox KG 024 User's Information Manual

Rooftop units 2, 2-1/2, 3, 4, 5, and 6 tons, 7-1/2, 8-1/2, 10 and 12-1/2 tons, 15, 17-1/2, 20 and 25 tons
Hide thumbs Also See for KG 024:
Table of Contents

Advertisement

Lubrication
All motors are lubricated at the factory. No further
lubrication is required.
Blower shaft bearings are prelubricated. For extended
bearing life, relubricate at least once every two years
with a lithium base grease, such as Alvania 3 (Shell Oil),
Chevron BRB2 (Standard Oil) or Regal AFB2 (Texas Oil).
Use a hand grease gun for relubrication. Add only enough
grease to purge through the bearings so that a bead of
grease appears at the seal lip contacts.
Manifold Pressures
Manifold pressures are shown in table 2. Refer to Figure
1, Figure 2, or Figure 3, or Figure 4 to locate pressure
ports.
MANIFOLD PRESSURES in w.g.
Unit
024, 030, 036, 048, 060,
074 Std./Med./High Heat
036, 048, 060, 074,
Dual Heat
092-300
Burners
Clean the burners as follows:
1 - Turn off the electrical power and the gas supply to
the unit.
2 - Remove the burner compartment access panel.
3 - Remove top burner box panel. See Figure 9 or
Figure 10.
4 - Remove screws securing burners to burner support
and lift the individual burners or the entire burner
assembly from the orifices. Clean as necessary.
Spark gap on ignition electrode must be properly
set. Refer to the Heating Adjustment section in the
installation instructions.
507350-06
8/2022
TABLE 2
Propane (LP)
Natural Gas
Gas
1st
2nd
1st
Stage
Stage
Stage
± 0.2
± 0.3
± 0.2
NA
3.5
NA
2.0
3.5
5.9
1.6
3.7
5.5
FLAME
SENSOR
BURNER
ASSEMBLY
GAS MANIFOLD
2nd
Stage
± 0.3
5 - Replace burners and screws securing burner.
10.5
Replace the top burner box panel and burner
compartment access panel.
10.5
6 - Turn on the electrical power and the gas supply to
10.5
the unit. Follow the operating instructions attached
to the unit and use the inspection port in the access
panel to check the flame.
GAS
VALVE
GAS
MANIFOLD
Page 7
BURNER BOX ASSEMBLY
024-074 UNITS
IGNITOR
FIGURE 9
BURNER BOX ASSEMBLY
092-300S UNITS
BURNER
ASSEMBLY
FLAME
SENSOR
FIGURE 10
GAS VALVE