Diagnostics, error and system alarms
5.4 Device-specific diagnostics with DP-V1
Byte 3: "Status specifier" variant
Table 5- 9
Bit no.
7...2
1...0
Bytes 4...62: Module-specific diagnostic data: General coding
This byte contains data with module-specific information that is described in the respective
module documentation. The particular module is identified by the slot (byte 2).
Bytes 4...62: Module-specific diagnostics for "Status type" and "Modul_Status"
In the case of the "Status type" variant of device-specific diagnostics from DP V1 slaves (see
byte 1, bit 7) and the "Module_Status" setting (see byte 1, bits 0...6) two status bits are
provided here for each slot (= module). Unneeded bits are set to 0.
Table 5- 10
Byte
4
5
...
62
The respective status bits are coded as follows:
Table 5- 11
Value
00
01
10
11
24
Structure of byte 3 of the device-specific diagnostics ("Status specifier" variant)
- Reserved -
Status_Specifier
0
1
2
3
Structure of the bytes for the module-specific diagnostic data
Bit
7
6
Module status 4
Module status 8
...
Module status 236
Meaning of the values of the status bits
Meaning
Data valid
Data invalid - error (e.g. short-circuit)
Data invalid - wrong module
Data invalid - no module plugged
Meaning
No further distinction
Status appears
Status disappears
- Reserved -
Bit assignment
5
4
Module status 3
Module status 2
Module status 7
Module status 6
...
Module status 235
Module status 234
Communication module CM DP (6ES7545-5DA00-0AB0)
3
2
1
Module status 1
Module status 5
...
Module status 233
Manual, 12/2014, A5E33619758-AB