Advertisement

Quick Links

Product Description
The Delta 16 Input Controller is a Native BACnet Application
Controller that is fully programmable (via GCL+) and
communicates on an RS-485 LAN using the MS/TP BACnet
protocol. The controller includes an easy to mount enclosure
and is designed for a wide range of monitoring applications
requiring no more than 16 inputs. A secondary LINKnet
network is also supported for up to 4 Delta BACstats or other
Delta LINKnet devices.
The 16 universal inputs are jumper configurable.
Important Information
ORCAview OWS and controller firmware must all be of the same version number to be
compatible. When upgrading any of these products from older versions (i.e. 3.22 or 3.30), you
must upgrade all the remaining products. Exception: UL 864 model, DAC-1600-UL864 can be
used with V3.33 and V3.40 firmware.
Package Contents
Product: DAC-1600 (Rev. 1.1)
DAC-1600 (Rev.1.1) Installation Guide
Related Documents
Delta Controls Wiring Guidelines
ORCAview Operator Guide
ORCAview Technical Reference Manual
Release Notes for related Firmware
I
NSTALLATION
UL 864 DAC-1600 Installation Guide
Updated November 17, 2015
G
UIDE
Document Edition 1.4
Document Edition 1.4

Advertisement

Table of Contents
loading

Summary of Contents for Delta DAC-1600

  • Page 1 ORCAview OWS and controller firmware must all be of the same version number to be compatible. When upgrading any of these products from older versions (i.e. 3.22 or 3.30), you must upgrade all the remaining products. Exception: UL 864 model, DAC-1600-UL864 can be used with V3.33 and V3.40 firmware.
  • Page 2 Wiring to and from the device shall be through power-limited circuits. Use only Core Components transformer, Model No. 120-024-100-2TF-CB, by Lectro Components Inc. to power the device. (Delta Part # 440008) Use only UL Listed Class 2 Power Supplies for auxiliary field devices.
  • Page 3 Document Edition 1.4 Mounting The DAC-1600 includes a plastic enclosure that can be quickly mounted with two screws (not provided). This controller should be mounted in an appropriate location within packaged equipment or another enclosure that meets code requirements. Page 3 of 12...
  • Page 4: Board Layout

    Delta Controls Board Layout Page 4 of 12...
  • Page 5: Controller Configuration

    Document Edition 1.4 Controller Configuration Derived Network Addressing The DNA jumper comes ON by default. This allows the controller to automatically configure a BACnet controller address. This should NOT be removed unless you are assigning a BACnet controller number through software.
  • Page 6: Wiring General

    Delta Controls Wiring General All wiring must conform to NEC and local codes and regulations. Use earth ground isolating step-down Class 2 transformers. Do not use autotransformers. Determine supply transformer rating by summing total VA of product and output loads.
  • Page 7: Network Communication

    Document Edition 1.4 Network Communication The controller communicates on an RS-485 LAN using the BACnet MS/TP protocol. Refer to Delta Controls Wiring Guidelines for further details. MS/TP (RS-485) Wiring For detailed information on MS/TP and LINKnet wiring refer to Delta Controls Wiring Guidelines.
  • Page 8: Input Wiring

    Delta Controls Input Wiring Inputs on the DAC-1600 controller follow the same general wiring requirements as other Delta Controls products. Recommended cable types should be used as listed below. Refer to the Delta Controls Wiring Guidelines for more details. Recommended Cable Type Where to Use 4-20mA, 10KΩ, and 10V input types...
  • Page 9 Document Edition 1.4 Indicators Function Description Power Controller Power This yellow LED turns on to indicate that the controller has power Indicator applied. Scan CPU Scan Indicator This red LED flashes at a rate relative to the CPU scan rate. Network MS/TP (RS485) The green LED flashes to indicate when the controller is...
  • Page 10: Product Specifications

    Maximum of 4 LINKnet controllers including up to two DFM controllers  Service RJ-11 Jack Port  Used with Delta Controls service tool devices (for example, CON-768) Inputs 16 Universal Inputs (10 bit), jumper configurable for the following input types:  0-5 VDC ...
  • Page 11: Ce Declaration Of Conformity

    Manufacturer's Address: 17850 56 Avenue Surrey, British Columbia Canada V3S 1C7 Declares that the product (s): Product Name: Delta Application Controller Model Numbers: DAC-1600 Product Options: Conforms to the following Product Specifications: EN 50081-1:1992 Generic Emission Standard EN 55022 Radiated and Conducted Emissions...
  • Page 12 Cet appareil numérique de la Classe B Respecte toutes les exigences du Règlement sur le matérial brouiller du Canada. This product conforms to the following UL requirements: UL916: Energy Management Equipment UL864*: Control Units and Accessories for Fire Alarm Systems, 9 Edition * - Applicable to DAC-1600-UL864 model only Page 12 of 12...