Siemens SITRANS LG270 Operating Instructions Manual page 58

Profibus pa rod and cable probe
Table of Contents

Advertisement

Failure (failure)
Code
Cause
Text message
F013
Sensor does not detect an echo dur-
ing operation
no measured val-
ue available
Antenna system dirty or defective
F017
Adjustment not within specification
Adjustment span
too small
F025
Index markers are not continuous-
ly rising, for example illogical value
Error in the line-
pairs
arization table
F036
Failed or interrupted software up-
date
No operable soft-
ware
F040
Hardware defect
Error in the elec-
tronics
F041
Cable probe broken or rod probe
defective
Probe loss
F080
General software error
General software
error
F105
The instrument is still in the start
phase, the measured value could
Measured value
not yet be determined
is determined
F113
Error in the internal instrument com-
munication
Communication
error
F125
Temperature of the electronics in the
non-specified range
Impermissible
electronics tem-
perature
58
Out of specification: The measured value is unreliable because an
instrument specification was exceeded (e.g. electronics temperature).
This status message is inactive by default.
Maintenance: Due to external influences, the instrument function
is limited. The measurement is affected, but the measured value is
still valid. Plan in maintenance for the instrument because a failure is
expected in the near future (e.g. due to buildup).
This status message is inactive by default.
Rectification
Check for correct mounting and/or
parameter settings
Clean or exchange process compo-
nent or antenna
Change adjustment according to the
limit values (difference between min.
and max. ≥ 10 mm)
Check linearisation table
Delete table/Create new
Repeat software update
Check electronics version
Exchanging the electronics
Send instrument for repair
Exchanging the electronics
Send instrument for repair
Check probe and exchange, if nec-
essary
Disconnect operating voltage briefly Bit 5
Wait for the end of the switch-on
phase
Duration up to approx. 3 minutes
depending on the version and pa-
rameter settings
Disconnect operating voltage briefly
Send instrument for repair
Check ambient temperature
Insulate electronics
Use instrument with higher temper-
ature range
SITRANS LG270 - Operating Instructions
DevSpec
Diagnosis Bits
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 13
Bit 6
-
Bit 7
PBD-51041506