ESIE17-19C
|
Part 4. Maintenance
4.2. Outdoor unit
4.2.1. General maintenance outdoor unit
1.
Outdoor unit coil
-
Straighten hair fins.
-
Clear coil from dust, leaves, etc. with a fin-comb, or compressed air/N2. Avoid bending or damaging of the Alu fins during
the cleaning process.
-
Remove the icicles during winter season. Use gloves to avoid injury and unit damage.
C
AUTION
Make sure not to bend the hair fins.
2.
Correlation of air-conditioner's operation status, pressure and running current.
COOLING
Dirty air filter
Short circuit of air inlet/outlet
Air mixed in refrigerant
Water mixed in refrigerant
Dirt mixed in refrigerant
Refrigerant shortage (gas)
* Water in the refrigerant freezes inside the electronic expansion valve and is basically the same phenomenon as pump down.
** Dirt in the refrigerant clogs filters inside the piping and is basically the same phenomenon as pump down.
*** Pressure differential between high and low pressure becomes low.
Page 100
Optimized Heating 4
Low pressure
Higher
Higher
Higher
Lower*
Lower**
Lower***
High pressure
Higher
Higher
Higher
Lower
Lower
Lower
4.2. Outdoor unit
Running current
Higher
Higher
Higher
Lower
Lower
Lower
19/08/19
|
Version 1.1