Occupancy Arbitration - Trane Tracer VV550 Installation, Operation And Maintenance Manual

Vav controller
Hide thumbs Also See for Tracer VV550:
Table of Contents

Advertisement

Table 27.Result of pressing the ON button in each occupancy mode
Controller
mode
Action
Occupied
ON button
pressed for one
second then
released
Unoccupied
ON button
mode
pressed for one
second then
released
Occupied
ON button
standby mode
pressed for one
second then
released
Occupied bypass
ON button
mode (timer not
pressed for one
expired)
second then
released

Occupancy Arbitration

Table 28
Table 28.Effective occupancy arbitration for Trane Comm5 devices
Communicated
Communicated
occupancy
occupancy
mode schedule
a
mode override
(heartbeat)
b
c
Occupied
X
b
c
Unoccupied
X
b
Bypass
Occupied
Unoccupied
Standby
Not present
b
c
Standby
X
CNT-SVX17G-EN
Result
Controller sets bypass timer to 120 minutes (default configured occupied bypass
time). The bypass timer starts to count down to zero. Concurrently, the controller
may change its current mode to unoccupied or occupied standby (possibly due to
a change based on the system time of day schedule). If it does, the controller
switches to occupied bypass mode for the remainder of the bypass time or until the
zone sensor CANCEL button is pressed. If the bypass timer counts down to zero, the
timed override is disabled.
Controller changes to occupied bypass mode. It sets the bypass timer to 120
minutes (default configured occupied bypass time). The timed override is disabled
either if the bypass timer counts down to zero or if the zone sensor CANCEL button
is pressed for one second then released.
Controller changes to occupied bypass mode. It sets the bypass timer to 120
minutes (default configured occupied bypass time). The timed override is disabled
either if the bypass timer counts down to zero or if the zone sensor CANCEL button
is pressed for one second then released.
Bypass timer set to 120 minutes (default configured occupied bypass time). When
the bypass timer counts down to zero, the timed override is disabled.
shows occupancy arbitration for Trane
Communicated
occupancy
mode sensor
(heartbeat)
c
X
c
X
c
X
c
X
c
X
Occupied
Unoccupied
Not present
c
X
®
Comm5 devices.
Occupancy
binary input
Bypass timer
c
c
X
X
c
X
Zero
Not zero
c
c
X
X
c
X
Zero
Not zero
c
X
Zero
Not zero
c
c
X
X
c
X
Zero
Not zero
c
Occupied
X
Unoccupied
Zero
Not zero
c
Not present
X
c
X
Zero
Not zero
Sequence of Operations
Reported
effective
occupancy
mode
Occupied
Unoccupied
Bypass
Occupied
Unoccupied
Bypass
Standby
Bypass
Occupied
Unoccupied
Bypass
Occupied
Unoccupied
Bypass
Occupied
Standby
Bypass
39