Outdoor Fan System Check; Main Circuit Short Check - Daikin 2MXS-W Series Service Manual

Multi-split type air conditioners
Table of Contents

Advertisement

SiUS122226E

8.11 Outdoor Fan System Check

Check No.19
DC motor

8.12 Main Circuit Short Check

Check No.20
Check to make sure that the voltage between (+) and (–) of the diode bridge (DB1) is about
0 V before checking
 Measure the resistance between the pins of the DB1 referring to the table below.
 If the resistance is  or less than 1 k, short circuit occurs on the main circuit.
Positive terminal (+) of
digital multimeter
Negative terminal (–) of
digital multimeter
Resistance is OK.
Resistance is NG.
Part 6 Service Diagnosis
Check the outdoor fan system.
Is
the outdoor fan
running?
YES
Outdoor fan system is functioning.
Fan motor lead
NO
wire connector
disconnected?
YES
Reconnect the connector.
~ (2, 3)
+ (4)
+ (4)
~ (2, 3)
several k ~ several M
0  or 
NO
Go to Check No. 16.
(R21195)
~ (2, 3)
– (1)
– (1)
~ (2, 3)
Check