Grounding The Fabric Interconnect - Cisco UCS 6500 Series Installation Manual

Fabric interconnecthardware
Hide thumbs Also See for UCS 6500 Series:
Table of Contents

Advertisement

Installing the Fabric Interconnect
c) Holding the chassis level, insert screws (12-24 or 10-32, depending on the rack type) in each of the two
front rack-mount brackets (using a total of six screws) and into the cage nuts or threaded holes in the
vertical rack-mounting rails (see the following figure).
d) Tighten the 10-32 screws to 20 in-lb (2.26 N·m) or tighten the 12-24 screws to 30 in-lb (3.39 N·m).
Step 5
If you attached a grounding wire to the chassis grounding pad, connect the other end of the wire to the facility
ground.

Grounding the Fabric Interconnect

The fabric interconnect chassis is automatically grounded when you properly install the fabric interconnect
in a grounded rack with metal-to-metal connections between the fabric interconnect and rack.
Note
You can also ground the chassis, which is required if the rack is not grounded, by attaching a customer-supplied
grounding cable. Attach the cable to the chassis grounding pad and the facility ground.
Warning
An electrical conducting path shall exist between the product chassis and the metal surface of the enclosure
or rack in which it is mounted or to a grounding conductor. Electrical continuity shall be provided by using
thread-forming type mounting screws that remove any paint or non-conductive coatings and establish a
metal-to-metal contact. Any paint or other non-conductive coatings shall be removed on the surfaces between
the mounting hardware and the enclosure or rack. The surfaces shall be cleaned and an antioxidant applied
before installation.
Statement 1024 Ground Conductor
This equipment must be grounded. To reduce the risk of electric shock, never defeat the ground conductor or
operate the equipment in the absence of a suitably installed ground conductor. Contact the appropriate electrical
inspection authority or an electrician if you are uncertain that suitable grounding is available.
Cisco UCS 6500 Series Fabric Interconnect Hardware Installation Guide

Grounding the Fabric Interconnect

23

Advertisement

Table of Contents
loading

Table of Contents