Instruction Manual Supplement
D104205X012
ATEX Hazardous Area Approvals
Fisher
FIELDVUE
Digital Valve Controllers
Hazardous Area Approvals and Special Instructions
for "Safe Use" and Installations in Hazardous Locations
Certain nameplates may carry more than one approval, and each approval may have unique installation/wiring
requirements and/or conditions of "safe use". These special instructions for "safe use" are in addition to, and may
override, the standard installation procedures. Special instructions are listed by approval type.
Note
This information supplements the nameplate markings affixed to the product and the DVC6200 Series quick start guide
(D103556X012), available from your
Always refer to the nameplate itself to identify the appropriate certification.
Approval information is for both aluminum and stainless steel constructions.
WARNING
Failure to follow these conditions of "safe use" could result in personal injury or property damage from fire or explosion
and area re‐classification.
WARNING
To avoid static discharge from the plastic cover when flammable gases or dust are present, do not rub or clean the cover
with solvents. To do so could result in a spark that may cause the flammable gases or dust to explode, resulting in personal
injury or property damage. Clean with a mild detergent and water only.
www.Fisher.com
DVC6200 Series
Emerson sales office
or at Fisher.com.
DVC6200 Digital Valve Controllers
November 2020
SIS

Advertisement

loading

Summary of Contents for Emerson Fisher FIELDVUE DVC6200 Series

  • Page 1 Note This information supplements the nameplate markings affixed to the product and the DVC6200 Series quick start guide (D103556X012), available from your Emerson sales office or at Fisher.com. Always refer to the nameplate itself to identify the appropriate certification. Approval information is for both aluminum and stainless steel constructions.
  • Page 2 Instruction Manual Supplement DVC6200 Digital Valve Controllers November 2020 D104205X012 Flameproof II 2 G WARNING Do not open while energized. Potential electrostatic charging hazard. See warning on page 1. Covered by Standards:  EN 60079-0:2012 + A11:2013  EN 60079-1:2014  DVC6200 and DVC6205 Series (HART HW1 & HW2, SIS, F Fieldbus, PROFIBUS) OUNDATION Ex d IIC T5 (Ta ≤...
  • Page 3 Instruction Manual Supplement DVC6200 Digital Valve Controllers D104205X012 November 2020 Type n II 3 G WARNING Do not open while energized. Potential electrostatic charging hazard. See warning on page 1. Covered by Standards:  EN 60079-0:2012 + A11:2013  EN 60079-15:2010 DVC6200 and DVC6205 Series (HART HW1 & HW2, SIS, F Fieldbus, PROFIBUS) OUNDATION Ex nC IIC T5 (Ta ≤...
  • Page 4: Intrinsically Safe

    Instruction Manual Supplement DVC6200 Digital Valve Controllers November 2020 D104205X012 Intrinsically Safe WARNING Potential electrostatic charging hazard. See warning on page 1. Covered by Standards:  EN 60079-0:2012 + A11:2013  EN 60079­11:2012 DVC6200 and DVC6205 Series (HART HW1 & HW2, SIS, F Fieldbus, PROFIBUS) OUNDATION II 1 GD...
  • Page 5 Instruction Manual Supplement DVC6200 Digital Valve Controllers D104205X012 November 2020 Figure 1. ATEX Loop Schematics—FIELDVUE DVC6200 HW2 and DVC6200 SIS ZONE 0, Ex ia IIC ZONE 0, Ex ia IIB HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION ZONE 20, Ex ia IIIC HW2 - WITH OR WITHOUT I/O PACKAGE DVC6200, DVC6200S Ex ia IIC Ex ia IIC...
  • Page 6 Instruction Manual Supplement DVC6200 Digital Valve Controllers November 2020 D104205X012 Figure 2. ATEX Loop Schematics—FIELDVUE DVC6205, DVC6205 SIS, and DVC6215 ZONE 0, Ex ia IIC ZONE 0, Ex ia IIB ZONE 20, Ex ia IIIC HW2 - WITH OR WITHOUT I/O PACKAGE DVC6205 ZONE 0, Ex ia IIC DVC6215...
  • Page 7 Instruction Manual Supplement DVC6200 Digital Valve Controllers D104205X012 November 2020 HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION Ex ia IIC Ex ia IIB LOOP TERMINALS LOOP TERMINALS Ui = 27.1 VDC Ui = 30 VDC Ii = 130 mA Ii = 130 mA Pi = 880 mW Pi = 1.0 W ATEX APPROVED BARRIER...
  • Page 8 Instruction Manual Supplement DVC6200 Digital Valve Controllers November 2020 D104205X012 Figure 3. ATEX Loop Schematics—FIELDVUE DVC6200f and DVC6200p ZONE 20 ZONE 0 Ex ia IIIC Ex ia IIC SURFACE HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION TEMP T AMB T CODE T AMB ZONE 0, Ex ia IIC T103_C ≤...
  • Page 9 Instruction Manual Supplement DVC6200 Digital Valve Controllers D104205X012 November 2020 Figure 4. ATEX Loop Schematics—FIELDVUE DVC6205f, DVC6205p, and DVC6215 ZONE 0, Ex ia IIC HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION ZONE 20, Ex ia IIIC DVC6205f, DVC6205p REMOTE FIELD FIELD WIRING WIRING TERMINAL TERMINAL BOX ZONE 0, Ex ia IIC LOOP...
  • Page 10 Instruction Manual Supplement DVC6200 Digital Valve Controllers November 2020 D104205X012 Figure 5. ATEX Loop Schematic—FIELDVUE DVC6200 HW1 HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION ZONE 0, Ex ia IIC ZONE 0, Ex ia IIB ZONE 20, Ex ia IIIC DVC6200, DVC6200S Ex ia IIC Ex ia IIC Ex ia IIC Ex ia IIB...
  • Page 11 Instruction Manual Supplement DVC6200 Digital Valve Controllers D104205X012 November 2020 Figure 6. Notes for ATEX Loop Schematics THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS TO ASSOCIATED APPARATUS NOT SPECIFI­ CALLY EXAMINED IN SUCH COMBINATION. THE CRITERIA FOR INTERCONNECTION IS THAT THE VOLTAGE (Vmax or Ui), THE CURRENT (Imax or Ii), AND THE POWER (Pmax or Pi) OF THE INTRINSICALLY SAFE APPARATUS MUST BE EQUAL TO OR GREATER THAN THE VOLT­...
  • Page 12 Fisher and FIELDVUE are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.