Emerson Fisher FIELDVUE DVC6200 HW1 Quick Start Manual

Emerson Fisher FIELDVUE DVC6200 HW1 Quick Start Manual

Digital valve controllers

Advertisement

Quick Start Guide
D103556X012
r
Fisher
FIELDVUE
Controllers
Contents
Step 4. Configure the DVC6200
Hazardous Area Approvals and Special Instructions for
"Safe Use"and Installations in Hazardous Locations
This quick start guide provides installation and initial setup information for DVC6200 Series digital valve controllers
DVC6200 Series Digital Valve
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
W9713
SIS
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
DVC6200 Digital Valve Controllers
3
4
19
23
33
. . . . . . .
35
. . . . . . .
43
August 2015

Advertisement

Table of Contents
loading

Summary of Contents for Emerson Fisher FIELDVUE DVC6200 HW1

  • Page 1: Table Of Contents

    Quick Start Guide DVC6200 Digital Valve Controllers D103556X012 August 2015 ™ Fisher FIELDVUE DVC6200 Series Digital Valve Controllers Contents Before You Begin ........Step 1.
  • Page 2 The following documents include product specifications, reference materials, custom setup information, maintenance procedures, and replacement part details. If a copy of any of these documents is needed scan or click the appropriate code below, contact your Emerson Process Management sales office, or visit our website at www.Fisher.com. DVC6200...
  • Page 3: Before You Begin

    Refer to Hazardous Area Approvals and Special Instructions for “Safe Use” and Installations in Hazardous Locations, on page 43, for approval specific safe use information. If you have any questions about these instructions, contact your Emerson Process Management sales office before proceeding. WARNING Avoid personal injury or property damage from sudden release of process pressure or bursting of parts.
  • Page 4: Step 1-Install The Dvc6200 On The Valve

    DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Step 1—Install the DVC6200 on the Valve Housing Variations The DVC6200 housing is available in two different configurations, depending on the actuator mounting method. Figure 1 shows the available configurations. Figure 1.
  • Page 5 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Use of Magnetic Tools with the DVC6200 D Magnetic Tip Screw Drivers – Magnetic tip screw drivers can be used to work on the DVC6200. However, they should not be brought in close proximity to the magnet assembly (located at the back of the instrument) during process operations.
  • Page 6: For Sliding-Stem Linear Actuators Proceed To

    DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Sliding‐Stem Linear Actuators Bracket Mounted Fisher 667 and 657 1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut off all pressure lines to the actuator, releasing all pressure from the actuator.
  • Page 7 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 D For air‐to‐close actuators (e.g. Fisher 657) vertically align the magnet assembly so that the center line of the alignment template is lined up as close as possible with the lower extreme of the valid travel range on the magnet assembly.
  • Page 8: Actuators Over 210 Mm (8.25 Inches Travel)

    DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Actuators over 210 mm (8.25 inches) Travel 1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut off all pressure lines to the pneumatic actuator, releasing all pressure from the actuator. Use lock‐out procedures to be sure that the above measures stay in effect while working on the equipment.
  • Page 9: Integral Mounted Fisher Actuators

    DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Integral Mounted Fisher Actuators 1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut off all pressure lines to the actuator, releasing all pressure from the actuator. Use lock‐out procedures to be sure that the above measures stay in effect while you work on the equipment.
  • Page 10: Air-To-Open (Gx)

    DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Air‐to‐Open (GX) Vertically align the magnet assembly so that the center line of the alignment template is lined up as close as possible with the upper extreme of the valid travel range on the magnet assembly. The magnet assembly should be positioned so that the index mark in the feedback slot of the DVC6200 housing is within the valid range on the magnet assembly throughout the range of travel.
  • Page 11 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Figure 8. Modifications for Fisher GX Actuator; Air‐to‐Open Construction Only INSTALL O‐RING INSTALL 1/4 NPT PLUG REMOVE R1/8 PLUG W9707 3. Install the plug (1/4 NPT, included in the mounting kit) to the external output pneumatic port A. 4.
  • Page 12: Air-To-Close (657 Size 30I - 70I Or Gx)

    DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Air‐to‐Close (657 size 30i - 70i and GX) Vertically align the magnet assembly so that the center line of the alignment template is lined up as close as possible with the lower extreme of the valid travel range on the magnet assembly. The magnet assembly should be positioned so that the index mark on the pole pieces (back of the DVC6200 housing) is within the valid range on the magnet assembly throughout the range of travel.
  • Page 13 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 2. Attach the digital valve controller to the actuator mounting pad. Note Use a 5 mm hex key to attach the digital valve controller the GX actuator mounting pad. Use a 13 mm socket or box end wrench to attach the digital valve controller to the 657 size 30i -70i actuator mounting pad. 3.
  • Page 14: For Quarter-Turn Rotary Actuators Proceed To

    DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Quarter-Turn Rotary Actuators Integral Mounted Fisher Actuators 1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut off all pressure lines to the pneumatic actuator, releasing all pressure from the actuator. Use lock‐out procedures to be sure that the above measures stay in effect while working on the equipment.
  • Page 15: Bracket Mounted

    DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 3. Mount the DVC6200 on the actuator as follows: D If required, a mounting adaptor is included in the mounting kit. Attach the adaptor to the digital valve controller, then attach the digital valve controller assembly to the actuator. The roller on the digital valve controller feedback arm will contact the actuator cam as it is being attached.
  • Page 16 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 2. Attach the magnet assembly to the actuator shaft. At mid‐travel, the flats on the magnet assembly should be approximately parallel to the channel on the back of the DVC6200 housing, as shown in figure 13. Figure 13.
  • Page 17 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 DVC6205 Remote Mount Base Unit Mounting For remote‐mounted digital valve controllers, the DVC6205 base unit ships separately from the control valve and does not include tubing, fittings or wiring. Pipestand Mounting 1.
  • Page 18 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Wall Mounting 1. Install the wall mounting screws by using the mounting bracket as a template. 2. Install the mounting bracket to the back of the base unit using the spacers and screws provided in the mounting kit. 3.
  • Page 19: Step 2-Connect The Pneumatic Tubing

    DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Step 2—Connect the Pneumatic Tubing Figure 16. Integral Mounting of a Fisher 67CFR Regulator on a FIELDVUE DVC6200 Digital Valve Controller OUTPUT A (1/4 NPT) 67CFR CAP SCREWS O‐RING NOTE: SUPPLY CONNECTION (1/4 NPT) 1 APPLY LUBRICANT OUTPUT B (1/4 NPT)
  • Page 20 Lubricant content is not to exceed 1 ppm weight (w/w) or volume (v/v) basis. Condensation in the air supply should be minimized. Check with an Emerson Process Management field office and industry instrument air quality standards for use with corrosive air or if you are unsure about the amount of air filtration or filter maintenance.
  • Page 21 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 WARNING Personal injury or property damage can occur from cover failure due to overpressure. Ensure that the housing vent opening is open and free of debris to prevent pressure buildup under the cover. This unit vents the supply medium into the surrounding atmosphere.
  • Page 22 18. Read and follow all local, regional, and federal wiring requirements for natural gas installations. Contact your Emerson Process Management sales office for information on obtaining a Natural Gas Certified, Single Seal DVC6200 digital valve controller.
  • Page 23: Step 3-Connect The Electrical Wires

    DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Step 3—Connect the Electrical Wires WARNING Select wiring and/or cable glands that are rated for the environment of use (such as hazardous area, ingress protection and temperature). Failure to use properly rated wiring and/or cable glands can result in personal injury or property damage from fire or explosion.
  • Page 24 The digital valve controller is normally powered over the bus from a power supply. Refer to the F fieldbus or OUNDATION PROFIBUS site planning guide, available from your Emerson Process Management sales office, for proper wire types, termination, length, grounding practices, etc. Note To avoid the valve going to an unknown position when power is applied, the unit digital valve controller is shipped from the factory with the transducer block mode Out of Service.
  • Page 25 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 4. Make connections to the ground terminal(s) following national and local codes and plant standards. As shown in figure 19, two ground terminals are available for connecting a safety ground, earth ground, or drain wire. The safety ground terminal is electrically identical to the earth ground.
  • Page 26 DVC6200 SIS instruction manual, available at www.FIELDVUE.com or from your local Emerson Process Management sales office additional information. The digital valve controller is normally powered by a control system output channel. Shielded cable will ensure proper operation in electrically noisy environments.
  • Page 27 DVC6200 SIS instruction manual, or contact your Emerson Process Management sales office. 5. Replace and hand tighten the cover on the terminal box. 6. For applications that require a Position Transmitter or Discrete Switch (page 28), Remote Feedback ™...
  • Page 28 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Position Transmitter or Discrete Switch The DVC6200 HART communicating device has an optional output circuit that can be configured as a 4­20 mA position transmitter or a discrete switch. Configuration of the output circuit requires the proper DIP switch electrical setting on the main electronics board (figure 22) and also must be enabled with a user interface tool.
  • Page 29 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Figure 23. FIELDVUE DVC6200 with Position Transmitter or Discrete Switch, Field Wiring Schematic 4 - 20 mA 8-30 VDC POWERED POSITION TRANSMITTER 4 - 20 mA MAX 30V DISCRETE SWITCH GE61668...
  • Page 30 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Remote Mount Feedback Unit The DVC6205 base unit is designed to receive a valve travel signal via the DVC6215 feedback unit. WARNING Do not place feedback wiring in the same conduit as other power or signal wiring. Personal injury or property damage, caused by wiring failure, can result if the feedback wiring connecting the base unit with the remote feedback unit shares a conduit with any other power or signal wiring.
  • Page 31 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Figure 24. Terminal Details for Connecting the Base Unit and Feedback Unit for Remote‐Mounted Digital Valve Controllers FEEDBACK CONNECTIONS TERMINAL BOX X0131 X0132 FEEDBACK UNIT GROUND BASE UNIT SCREW TO FEEDBACK UNIT TERMINAL 1 TO FEEDBACK UNIT TERMINAL 2 TO FEEDBACK UNIT TERMINAL 3 TO FEEDBACK UNIT TERMINAL 4...
  • Page 32 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Smart Wireless THUM Adapter Refer to the Smart Wireless THUM Adapter quick installation guide (00825­0100­4075) for additional information. Note The recommended mounting orientation for the THUM Adapter is vertically up, as shown in figure 26, for optimal wireless communication range.
  • Page 33 Descriptions (DD, EDD), ValveLink software, Device Type Manager (DTM), or GSD. Refer to table 1 below. Contact your local Emerson Process Management sales office to ensure that you have the latest software version or for information on locating the necessary files.
  • Page 34 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 2. Apply pneumatic supply pressure to the digital valve controller and adjust the supply pressure regulator according to the actuator requirements and limitations. 3. Apply electrical power to the digital valve controller. 4.
  • Page 35: Special Instructions For Safety Instrumented Systems

    DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Special Instructions for Safety Instrumented Systems DVC6200 SIS instruments are identified by an SIS label on the terminal box cover. Refer to the Safety manual further information regarding the design, installation, and operation of the DVC6200 SIS product. The following section illustrates typical installation scenarios for a DVC6200 SIS.
  • Page 36 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 An optional local control panel (LCP100), shown in figure 29, can be installed to provide manual operation of the DVC6200 SIS instrument. Refer to the LCP100 instruction manual (D103272X012) for further information. Note If the LCP100 is connected to a DVC6200 SIS in a zone 1 explosion-proof “d”...
  • Page 37 The pilot pressure must be at least 15 psig higher than the solenoid valve line pressure. For more information, refer to the ASCO catalog or contact your Emerson Process Management sales office. 1. Install the solenoid valve on the actuator casing or actuator yoke.
  • Page 38 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 3. If the DVC6200 SIS and solenoid valve are powered separately: D Connect the logic solver output card +/­ terminals to the corresponding solenoid valve +/­ wires. D Connect the logic solver (or DCS) output card +/­ terminals to the corresponding DVC6200 SIS LOOP +/­ terminals.
  • Page 39 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 De-Energize to Trip (DETT) DVC6200 SIS, no Solenoid Valve In a typical de­energize to trip application without a solenoid valve, the logic solver trip signal de­energizes the digital valve controller to 4 mA (or 0 VDC). This drives the digital valve controller to the no output pressure condition. As a result, the safety valve moves to its no­air, fail safe position.
  • Page 40 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 2. If the DVC6200 SIS and solenoid valve are powered together: D Install an LC340 line conditioner to allow HART communication over the segment. Refer to the LC340 instruction manual for more information.
  • Page 41 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 DVC6200 SIS for PST only and De-Energize to Trip (DETT) Solenoid Valve In this application, the logic solver trip signal de­energizes the solenoid valve, which opens the solenoid vent valve. The DVC6200 SIS is configured as energize to trip (ETT) and uses a reverse acting relay (Relay B) to drive the digital valve controller to the no output pressure condition.
  • Page 42 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Solenoid Valve Health Monitoring If a solenoid valve is installed between the DVC6200 SIS pressure output and the actuator, the control valve assembly can be configured to verify the operation of the solenoid valve. This applies to single­acting actuator applications only. The “unused”...
  • Page 43 Note This information supplements the nameplate markings affixed to the product. Always refer to the nameplate itself to identify the appropriate certification. Contact your Emerson Process Management sales office for approval/certification information not listed here. Approval information is for both aluminum and stainless steel constructions.
  • Page 44 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Ordinary Locations Approval Complies with general electrical safety CAN/CSA­C22.2 No. 61010­1­2004 SELV, conduit connected, Enclosure Type 4X, IP66, Installation Category I, Pollution Degree 4 DVC6200 Series (HART HW1, F fieldbus, PROFIBUS) OUNDATION Rated Input 9-30 VDC, 4-20 mA -52_C to + 80_C Ambient...
  • Page 45 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Intrinsically Safe Class I, Division 1, Groups A,B,C,D Class II, Division 1, Groups E,F,G Class III, Division 1 Ex ia IIC Type 4X, IP66 Single Seal Device (HART HW2 and SIS pending) Rated input 30 V DC max, 20 mA - 52 _C <...
  • Page 46 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Figure 38. CSA Loop Schematics—FIELDVUE DVC6200 HW2 and DVC6200 SIS HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION CLASS I, ZONE 0, GROUP IIC CLASS I, DIV 1, GROUPS ABCD CLASS II, DIV 1, GROUPS EFG CLASS III HW2 - WITH OR WITHOUT I/O PACKAGE DVC6200, DVC6200S...
  • Page 47 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Figure 39. CSA Loop Schematics FIELDVUE DVC6205, DVC6205 SIS, and DVC6215 HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION CLASS I, ZONE 0, GROUP IIC CLASS I, DIV 1, GROUPS ABCD CLASS II, DIV 1, GROUPS EFG CLASS III HW2 - WITH OR WITHOUT I/O PACKAGE DVC6205...
  • Page 48 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Figure 40. CSA Loop Schematics—FIELDVUE DVC6200f and DVC6200p NON‐HAZARDOUS LOCATION HAZARDOUS LOCATION CLASS I, ZONE 0, GROUP IIC CLASS I, DIV 1, GROUPS ABCD CLASS II, DIV 1, GROUPS EFG T CODE T (amb) CLASS III...
  • Page 49 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Figure 41. CSA Loop Schematics FIELDVUE DVC6205f, DVC6205p, and DVC6215 NON‐HAZARDOUS LOCATION HAZARDOUS LOCATION CLASS I, ZONE 0, GROUP IIC CLASS I, ZONE 0, GROUP IIC CLASS I, DIV 1, GROUPS ABCD CLASS I, DIV 1, GROUPS ABCD CLASS II, DIV 1, GROUPS EFG CLASS II, DIV 1, GROUPS EFG...
  • Page 50 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Figure 42. Notes for CSA Loop Schematics THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS TO ASSOCIATED APPARATUS NOT SPECIFICALLY EXAMINED IN SUCH COMBINATION. THE CRITERIA FOR INTERCONNECTION IS THAT THE VOLTAGE (Vmax or Ui), THE CURRENT (Imax or Ii), AND THE POWER (Pmax or Pi) OF THE INTRINSICALLY SAFE APPARATUS MUST BE EQUAL TO OR GREATER THAN THE VOLTAGE (Voc or Uo), AND THE CURRENT (Isc or Io), AND THE POWER(Po) DEFINED BY THE ASSOCIATED APPARATUS.
  • Page 51 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Explosion-proof, Dust-Ignition proof, Non-Incendive, Suitable for Use DVC6200 and DVC6205 Series (HART HW1 & HW2, SIS, F , PROFIBUS) OUNDATION FIELDBUS XP: Class I, Division 1, Groups B,C,D DIP: Class II, III, Division 1, Groups E,F,G NI: Class I, Division 2, Groups A,B,C,D S: Class II, III, Division 2, Groups F,G T5 Ta = 80°C, T6 Ta = 75°C...
  • Page 52 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Figure 43. FM Loop Schematic—FIELDVUE DVC6200 HW1 NON‐HAZARDOUS LOCATION HAZARDOUS LOCATION I.S. CLASS I,II,III, DIV 1, GROUPS ABCDEFG N.I. CLASS I, DIV 2, GROUPS ABCD DVC6200, DVC6200S Vmax = 30 VDC Imax = 226 mA FM APPROVED BARRIER Ci = 5 nF...
  • Page 53 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Figure 44. FM Loop Schematics—FIELDVUE DVC6200 HW2 and DVC6200 SIS HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION I.S. CLASS I, II, III DIV 1, GROUPS ABCDEFG N.I. CLASS I, DIV 2, GROUPS ABCD HW2 - WITH OR WITHOUT I/O PACKAGE DVC6200, DVC6200S LOOP TERMINALS...
  • Page 54 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Figure 45. FM Loop Schematics—FIELDVUE DVC6205, DVC6205 SIS, and DVC6215 HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION I.S. CLASS I, II, III DIV 1, GROUPS ABCDEFG N.I. CLASS I, DIV 2, GROUPS ABCD HW2 - WITH OR WITHOUT I/O PACKAGE DVC6205 REMOTE...
  • Page 55 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Figure 46. FM Loop Schematics—FIELDVUE DVC6200f and DVC6200p HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION I.S. CLASS I,II,III DIV 1, GROUPS ABCDEFG T CODE T (amb) N.I. CLASS I, DIV 2, GROUPS ABCD ≤...
  • Page 56 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Figure 47. FM Loop Schematics—FIELDVUE DVC6205f, DVC6205p, and DVC6215 HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION I.S. CLASS I, II, III DIV 1, GROUPS ABCDEFG I.S. CLASS I, II, III DIV 1, GROUPS ABCDEFG N.I.
  • Page 57 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Figure 48. Notes for FM Loop Schematics THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS TO ASSOCIATED APPARATUS NOT SPECIFICALLY EXAMINED IN SUCH COMBINATION. THE CRITERIA FOR INTERCONNECTION IS THAT THE VOLTAGE (Vmax OR Ui), THE CURRENT (Imax OR Ii), AND THE POWER (Pmax or Pi) OF THE INTRINSICALLY SAFE APPARATUS MUST BE EQUAL TO OR GREATER THAN THE VOLTAGE (Voc OR Uo), AND THE CURRENT (Isc OR Io), AND THE POWER(Po) DEFINED BY THE ASSOCIATED APPARATUS.
  • Page 58 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 ATEX Flameproof II 2 G WARNING Do not open while energized. Potential electrostatic charging hazard. See warning on page 3. DVC6200 and DVC6205 Series (HART HW1 & HW2, SIS, F , PROFIBUS) OUNDATION FIELDBUS Ex d IIC T5 (Ta ≤...
  • Page 59 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Intrinsically safe when connected per control drawing GE60771, as shown in the following figures DVC6200 HW1 ......... . . figure 49 and 54 DVC6200 HW2, DVC6200 SIS .
  • Page 60 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Figure 50. ATEX Loop Schematics—FIELDVUE DVC6200 HW2 and DVC6200 SIS NON‐HAZARDOUS LOCATION HAZARDOUS LOCATION ZONE 0, Ex ia IIC ZONE 20, Ex ia IIIC HW2 - WITH OR WITHOUT I/O PACKAGE DVC6200, DVC6200S LOOP TERMINALS Ui = 30 VDC...
  • Page 61 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Figure 51. ATEX Loop Schematics—FIELDVUE DVC6205, DVC6205 SIS, and DVC6215 HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION ZONE 0, Ex ia IIC ZONE 20, Ex ia IIIC ZONE 0, Ex ia IIC HW2 - WITH OR WITHOUT I/O PACKAGE DVC6215 DVC6205 T CODE...
  • Page 62 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Figure 52. ATEX Loop Schematics—FIELDVUE DVC6200f and DVC6200p ZONE 20 ZONE 0 Ex ia IIIC Ex ia IIC HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION SURFACE T AMB T CODE T AMB TEMP ZONE 0, Ex ia IIC ≤...
  • Page 63 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Figure 53. ATEX Loop Schematics—FIELDVUE DVC6205f, DVC6205p, and DVC6215 HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION ZONE 0, Ex ia IIC ZONE 20, Ex ia IIIC ZONE 0, Ex ia IIC DVC6205f, DVC6205p DVC6215 Ui = 30 VDC Uo = 24 VDC...
  • Page 64 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Figure 54. Notes for ATEX Loop Schematics THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS TO ASSOCIATED APPARATUS NOT SPECIFICALLY EXAMINED IN SUCH COMBINATION. THE CRITERIA FOR INTERCONNECTION IS THAT THE VOLTAGE (Vmax or Ui), THE CURRENT (Imax or Ii), AND THE POWER (Pmax or Pi) OF THE INTRINSICALLY SAFE APPARATUS MUST BE EQUAL TO OR GREATER THAN THE VOLTAGE (Voc or Uo), AND THE CURRENT (Isc or Io), AND THE POWER(Po) DEFINED BY THE ASSOCIATED APPARATUS.
  • Page 65 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 IECEx Flameproof WARNING Do not open while energized. Potential electrostatic charging hazard. See warning on page 3. DVC6200 and DVC6205 Series (HART HW1 & HW2, SIS, F , PROFIBUS) OUNDATION FIELDBUS Ex d IIC T5 (Ta ≤...
  • Page 66 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Intrinsically Safe WARNING Potential electrostatic charging hazard. See warning on page 3. Ex ia IIC IP66 Intrinsically safe when connected per drawing GE42990, as shown in the following figures DVC6200 HW1 .
  • Page 67 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Figure 56. IECEx Loop Schematics—FIELDVUE DVC6200 HW2 and DVC6200 SIS NON‐HAZARDOUS LOCATION HAZARDOUS LOCATION ZONE 0, Ex ia IIC HW2 - WITH OR WITHOUT I/O PACKAGE DVC6200, DVC6200S LOOP TERMINALS Vmax = 30 VDC Imax = 130 mA IECEx APPROVED BARRIER...
  • Page 68 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Figure 57. IECEx Loop Schematics—FIELDVUE DVC6205, DVC6205 SIS, and DVC6215 HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION ZONE 0, Ex ia IIC HW2 - WITH OR WITHOUT I/O PACKAGE DVC6205 REMOTE FIELD WIRING FIELD WIRING TERMINAL BOX TERMINAL BOX...
  • Page 69 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Figure 58. IECEx Loop Schematics—FIELDVUE DVC6200f and DVC6200p HAZARDOUS LOCATION NON‐HAZARDOUS LOCATION T CODE T (amb) ≤ 80_C ZONE 0, Ex ia IIC ≤ 77_C DVC6200F, DVC6200FS DVC6200P, DVC6200PS ≤ 62_C Ui = 24 VDC Ii = 380 mA Ci = 5 nF...
  • Page 70 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Figure 59. IECEx Loop Schematics—FIELDVUE DVC6205f, DVC6205p, and DVC6215 NON‐HAZARDOUS LOCATION HAZARDOUS LOCATION ZONE 0, Ex ia IIC ZONE 0, Ex ia IIC DVC6205f, DVC6205p DVC6215 Ui = 30 VDC Uo = 24 VDC Ui = 24 VDC Ii = 226 mA...
  • Page 71 DVC6200 Digital Valve Controllers Quick Start Guide August 2015 D103556X012 Figure 60. Notes for IECEx Loop Schematics THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS TO ASSOCIATED APPARATUS NOT SPECIFICALLY EXAMINED IN SUCH COMBINATION. THE CRITERIA FOR INTERCONNECTION IS THAT THE VOLTAGE (Vmax OR Ui), THE CURRENT (Imax OR Ii), AND THE POWER (Pmax or Pi) OF THE INTRINSICALLY SAFE APPARATUS MUST BE EQUAL TO OR GREATER THAN THE VOLTAGE (Voc OR Uo), AND THE CURRENT (Isc OR Io), AND THE POWER (Po) DEFINED BY THE ASSOCIATED APPARATUS.
  • Page 72: Www.fisher.com

    Fisher, FIELDVUE, ValveLink, and THUM are marks owned by one of the companies in the Emerson Process Management business unit of Emerson Electric Co. Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. HART and the HART logo are registered trademarks of FieldComm Group.