System Function And Sequence Of Operation (127A/226A/Ca17/Ch17/Ba17/Bh17); Compressor Operation; Quiet Shift; Quiet Shift-2 (Non-Communicating) - Bryant Base Series Application Manual And Service Manual

Residential air conditioners and heat pumps
Table of Contents

Advertisement

Residential Air Conditioners and Heat Pumps Using R-22 and Puron® Refrigerant: Application Guideline and Service Manual
System function and Sequence Of Operation
(127A/226A/CA17/CH17/BA17/BH17)
NOTE: Defrost control board is equipped with 5 minute lockout timer
that is initiated upon any interruption of power.
Turn on power to indoor and outdoor units. Transformer is energized.
These models utilize a 2-stage indoor thermostat. With a call for first
(low) stage cooling or heating, the outdoor fan and low-stage
compressor are energized. If low-stage cannot satisfy cooling or heating
demand, high-stage is energized by the second (high) stage of the indoor
thermostat. After the second stage is satisfied, the unit returns to
low-stage operation until second stage is required again. When both,
first and second stage cooling or heating are satisfied, the compressor
will shut off.
Cooling
With first stage cooling, Y and O are powered on; and with second stage
cooling, Y2, Y and O are powered on. The O energizes the reversing
valve, switching it to cooling position. The Y signal sends low voltage
through the safeties and energizes the T1 terminal on the circuit board.
If the compressor has been off for 5 minutes, or power has not been
cycled for 5 minutes, the OF2 relay and T2 terminal will energize. This
will close the contactor and start the outdoor fan motor and compressor.
When the cycle is complete, Y is turned off, stopping the compressor
and outdoor fan. The 5 minute time guard begins counting. Compressor
will not come on until this delay expires. In the event of a power
interruption, the time guard will not allow another cycle for 5 minutes.
Heating
With first stage heating, Y is powered on; with second stage heating, Y2
and Y are powered on. The Y signal sends low voltage through the
safeties and energizes the T1 terminal on the circuit board. If the
compressor has been off for 5 minutes or power has not been cycled for
5 minutes, the OF2 relay and T2 terminal will energize. This will close
the contactor and start the outdoor fan motor and compressor.
When the cycle is complete, Y is turned off, stopping the compressor nd
outdoor fan. The 5 minute time guard begins counting. Compressor will
not come on until this delay expires.
interruption, the time guard will not allow another cycle for 5 minutes.

Compressor Operation

The basic scroll design has been modified with the addition of an
internal unloading mechanism that opens a by-pass port in the first
compression pocket, effectively reducing the displacement of the scroll.
The opening and closing of the by-pass port is controlled by an internal
electrically operated solenoid. The modulated scroll uses a single step of
unloading to go from full capacity to approximately 67% capacity.
A single speed, high efficiency motor continues to run while the scroll
modulates between the two capacity steps. Modulation is achieved by
venting a portion of the gas in the first suction pocket back to the low
side of the compressor, thereby reducing the effective displacement of
the compressor.
Full capacity is achieved by blocking these ports, thus increasing the
displacement to 100%. A DC solenoid in the compressor controlled by a
rectified 24 volt AC signal in the external solenoid plug moves the slider
ring that covers and uncovers these ports.
The port covers are arranged in such a manner that the compressor
operates at approximately 67% capacity when the solenoid is not
energized and 100% capacity when the solenoid is energized. The
loading and unloading of the two step scroll is done "on the fly" without
shutting off the motor between steps.
NOTE: 67% compressor capacity translates to approximately 75%
cooling or heating capacity at the indoor coil.
The compressor will always start unloaded and stay unloaded for five
seconds even when the thermostat is calling for high stage capacity.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
In the event of a power
63

Quiet Shift

Quiet shift is a field selectable defrost mode (factory set to OFF), which
will eliminate occasional noise that could be heard at the start of defrost
cycle and restarting of heating cycle. It is selected by placing DIP switch
3 on defrost board (see
Fig.
47) in the ON position.
When Quiet Shift switch is placed in ON position, and a defrost is
initiated, the following sequence of operation will occur. Reversing
valve will energize, compressor will turn off for 30 seconds, and then
turn back on to complete defrost. At the start of heating after conclusion
of defrost, reversing valve will de-energize, compressor will turn off for
another 30 seconds, and the fan will turn off for 40 seconds, before
starting in the heating mode.
HK32EA008/010 Defrost Control
The HK32EA008 defrost control is used in some non-communicating
heat pumps and has all the same functionality, speedups, and
troubleshooting as the HK32EA003 except for the forced defrost timing
when Quiet Shift-2 is enabled.

Quiet Shift-2 (non-communicating)

Quiet shift-2 is a field selectable defrost mode (factory set to OFF),
which will reduce the occasional noise that could be heard at the start of
defrost cycle and restarting of heating cycle. It is selected by placing DIP
switch 3 on defrost board in the ON position.
When Quiet Shift-2 switch is placed in ON position, and defrost is
initiated, the following sequence of operation will occur: The
compressor will be de-energized for approximately 1 minute, then the
reversing valve will be energized. A few seconds later, the compressor
will be re-energized and the normal defrost cycle starts. Once defrost
termination conditions have been met, the following sequence will
occur: The compressor will be de-energized for approximately 1 minute,
then the reversing valve will be de-energized. A few seconds later, the
compressor will be re-energized and the normal heating cycle starts.

Defrost

The defrost control is a time/temperature control which has field
selectable settings of 30, 60, 90, or 120 minutes, factory set to 90
minutes. These settings represent the amount of time that must pass after
closure of the defrost thermostat before the defrost sequence begins.
The defrost thermostat senses coil temperature throughout the heating
cycle. When the coil temperature reaches the defrost thermostat setting
of approximately 32_F/0_C, it will close, which energizes the DFT
terminal and begins the defrost timing sequence. When the DFT has
been energized for the selected time, the defrost cycle begins. Defrost
cycle is terminated when defrost thermostat opens at approximately
65_F/18.3_C, or, or automatically after 10 minutes.

Defrost Speedup

To initiate a forced defrost, speedup pins (J1) must be shorted with a flat
head screwdriver for 5 seconds and RELEASED. If the defrost
thermostat is open, a short defrost cycle will be observed (actual length
depends on Quiet Shift switch position). When Quiet Shift is off, only a
short 30 second defrost cycle is observed. With Quiet Shift ON, the
speedup sequence is one minute; 30 second compressor off period
followed by 30 seconds of defrost with compressor operation. When
returning to heating mode, the compressor will turn off for an additional
30 seconds and the fan for 40 seconds.
If the defrost thermostat is closed, a complete defrost cycle is initiated. If
the Quiet Shift switch is turned on, the compressor will be turned off for
two 30 second intervals as explained previously.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents