Commissioning
Integrating the Vitotronic Control Unit into LON
Example: Single boiler system with Vitotronic 300, Vitotronic 200-H heating circuit control unit downstream and
Vitogate 300, type BN/MB
Vitotronic 300
Participant no. 1
Code "77:1"
Control unit is fault manager
Code "79:1"
Viessmann system number
Code "98:1"
LON participant fault monitoring
Code "9C:20"
Updating LON Participant List
Carrying out Participant Check
14
The LON communication module (accessory*) must be
installed into the Vitotronic control unit.
* Depending on the relevant control, this may be an
additional accessory item.
Note: The data transfer via LON can take several minute
LON system number and participant number
Set LON system number, LON participant number and
further functions via code 2.
Note: In the same LON system, each number an only be
Vitotronic 200-H
Participant no. 10
Code "77:10"
Control unit is not fault manager.
Code "79:0"
Viessmann system number
Code "98:1"
LON participant fault monitoring
Code "9C:20"
Vitogate 300 Installation and Service
Refer to the relevant Vitotronic control unit
Service Instructions and the following table.
allocated once.
Only one Vitotronic control unit per system may
be programmed as the fault manager.
Delivered condition Vitogate 300:
Participant no. 97
Device is fault manager.
Refer to the relevant Vitotronic control unit
Installation and Service Instructions.
Refer to the relevant Vitotronic control unit
Installation and Service Instructions.
Vitogate 300
--
--