Enabling Pwrgenerator; Pwrgenerator States And Settings - Generac Power Systems PWRgenerator 9 kW Installation Manuallines

Air-cooled generator
Hide thumbs Also See for PWRgenerator 9 kW:
Table of Contents

Advertisement

Control Panel Startup / Testing

Enabling PWRgenerator

Proceed as follows to enable PWRgenerator:
1. Set generator MLCB (generator disconnect) to ON
(CLOSED).
2. Set PWRgenerator to AUTO using PWRgenerator
control panel. PWRgenerator will be automatically
enabled when transitioned from OFF to AUTO.
3. Navigate to PWRgenerator device page on PWR-
cell Inverter control panel.
4. Verify status is "Standby."
Proceed as follows if PWRgenerator needs to be manu-
ally enabled at inverter control panel:
1. Navigate to PWRgenerator device page and press
center button.
Setting
STANDBY
CONNECTING
GENERATOR
RUNNING
DISCONNECTING
GENERATOR
DISABLED
Setting
AutoStrtSoC
AutoStopSoC
36
TABLE 1. PWRgenerator States
PWRgenerator is enabled and set to AUTO at generator control panel. When genera-
tor control panel moves from OFF to AUTO, PWRgenerator state at PWRcell Inverter
control panel should automatically be changed to STANDBY.
PWRgenerator does not produce power when in STANDBY.
Generator start conditions have been met and PWRgenerator has begun its standard
startup sequence. PWRgenerator will progress to a RUNNING state when startup
sequence is complete.
PWRgenerator is running and is generating power.
Generator stop conditions have been met and PWRgenerator has begun its standard
cool-down sequence. PWRgenerator will return to a STANDBY state when generator
cool-down is complete.
PWRgenerator is not enabled. See
TABLE 2. PWRgenerator Settings
Battery state of charge (SoC) where PWRgenerator is prompted to start and deliver
power. PWRgenerator must be in AUTO for this setpoint to have effect.
Default value is 25%.
Battery SoC where PWRgenerator is prompted to stop delivering power and enter
standby state. PWRgenerator must be in AUTO for this setpoint to have effect.
Default value is 95%.
2. Select "Enable" and press center button. Use right
arrow key and press center button to confirm.
3. Verify on PWRgenerator device page PWRgenera-
tor status reads "Standby."

PWRgenerator States and Settings

The PWRgenerator device page on the PWRcell Inverter
control panel allows users to view current operating sta-
tus of the PWRgenerator, manually change the operating
state, and view or alter configurable settings. See
Table 1
for a detailed list of states which may be dis-
played on PWRgenerator device page. See
detailed list of PWRgenerator settings found in "Mod Set-
tings" menu of PWRgenerator device page.
Description
Enabling PWRgenerator
Description
Installation Guidelines for PWRgenerator Air-Cooled Generators
Table 2
for a
for further details.

Advertisement

Table of Contents
loading

Table of Contents