Electrical Connections

Control Wiring

Table 6-1. Electrical Wiring Connection Points
ID
Description
A1
Power lug RE+
A2
Power lug RE-
B
Ground stud
C
Ground lug
Table 6-2. Customer Wiring Connections
Terminal
Identification
REbus Positive (DC) REbus RED positive wire
REbus Negative
REbus BLACK negative wire
(DC)
28
Figure 6-1. Electrical Wiring Connections
Wire Description
A1
B
.
Table 6-3. REbus and Ground Connections
(Copper Conductors)
See national and/or local codes to verify correct wire sizes.
Conductor
Description
Range
Power wire
6 to 8 AWG
terminals
Large ground lug
4 to 14 AWG
Installation Guidelines for PWRgenerator Air-Cooled Generators
A2
C
Torque Spec
120 in-lbs (13.56 Nm)
120 in-lbs (13.56 Nm)