Section 7: Control Panel Startup / Testing
Control Panel Interface
The control panel interface is located under the enclo-
sure lid. Verify both left and right side locks are unlocked
before attempting to lift enclosure lid. Open lid as
directed in
Opening the
Using the AUTO/MANUAL/OFF Buttons
Button
Description Of Operation
AUTO
Activates fully automatic system operation. Auto-
matic operation allows unit to automatically start
and exercise generator according to exercise
timer settings (see
Timer).
OFF
Shuts down engine and also prevents automatic
operation and exercise of unit.
MANUAL
Cranks and starts generator. Transfer to standby
power will not occur unless there is a utility fail-
ure. Generator supplies power to REbus.
Figure 7-1. Generator Control Panel
Generator Setup
The controller illuminates when battery power is applied
to the generator during the installation process. Genera-
tor must be activated before it will automatically run in the
event of a power outage.
Activation
To activate the generator, go to
and follow the instructions.
Activation is a simple, one-time process. The generator
will not prompt to activate again once the unit is acti-
vated, even if the generator battery, and fuse are discon-
nected.
Proceed as follows after activating generator on-line:
Installation Guidelines for PWRgenerator Air-Cooled Generators
Lid.
Setting The Exercise
www.activategen.com
1. The display interface will launch Install Wizard
upon first power-up of the generator.
2. Follow on-screen instructions on generator along
with Quick Start Guide supplied with unit.
3. Follow on-screen instructions to complete the
Install Wizard.
NOTE: See
Figure
sage shown below, press ESC and then ENTER to reset
to Install Wizard.
NOT ACTIVATED!
Figure 7-2. Not Activated Screen
NOTE: Generator can only be placed in AUTO mode
after completing activation process.
000425
Control Panel Startup / Testing
7-2. If generator screen shows mes-
XXX (H)
009102
31