Finally, the F-DQ module is configured to control the redundant contactors. Here again, the
F parameters remain unchanged (default setting). The setting of the safe monitoring can be
taken from the following figure.
Figure 4-16
Note
Unused channels, such as channels 1 to 3 of the F-DQ module, should be deactivated for
reasons of clarity and improved performance. For this purpose, the check is removed from
"Activated" for the corresponding channels. For the F-CM AS-i Safety ST module, the user
must activate the input channels required for the configured AS-i slaves.
Safety engineering with AS‑Interface in the SIMATIC ET 200SP, including typical circuit diagram
Function Manual, 08/2020, A5E44991382002A/RS-AB/002
Configuration of the F-DQ module
Circuit diagram example
4.4 TIA Portal configuration
41