Refrigerant Replacement Procedure - Trane CXAO Installation Operation & Maintenance

Air to water reversible scroll heat pumps, air to water reversible screw heat pumps
Table of Contents

Advertisement

Refrigerant replacement procedure

°C
Bar
-20
4,04
-18
4,35
-16
4,67
-14
5,02
-12
5,38
-10
5,76
-8
6,16
-6
6,58
-4
7,03
-2
7,50
0
7,99
2
8,50
4
9,04
44
Table Pressure/Temperature of HFC-410
°C
Bar
6
9,61
8
10,20
10
10,82
12
11,46
14
12,14
16
12,85
18
13,58
20
14,35
22
15,15
24
15,99
26
16,85
28
17,76
30
18,70
°C
Bar
32
19,68
34
20,69
36
21,75
38
22,84
40
23,98
42
25,16
44
26,39
46
27,65
48
28,97
50
30,33
52
31,75
54
33,21
56
34,72
°C
Bar
58
36,29
60
37,91
62
39,59
64
41,32
66
43,11
68
44,97
RF-SVX003A-GB