Tripp Lite SmartOnline S3MX Owner's Manual page 60

3-phase ups systems
Hide thumbs Also See for SmartOnline S3MX:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
7. UPS Operation
Step 5
Turn OFF the Q4 Maintenance Bypass breaker (all models).
Step 6
Secure the mechanical locking plate to the Q4 Maintenance Bypass breaker (all models).
Step 7
Press Power ON/OFF button for 2 seconds until a beep is heard, then release to start the inverter.
The critical load is now supported in Line Mode.
Step 8
ON
OFF
Q4
Maintenance Bypass
S3M100KX/S3M100KXD
S3M120KX/S3M120KXD
(100 kVA/200 kVA) Models
Q4
Maintenance Bypass
S3M100KX/S3M100KXD
S3M120KX/S3M120KXD
(100 kVA/200 kVA) Models
60
OFF
ON
Q4
Maintenance Bypass
S3M160KX/S3M160KXD
S3M200KX/S3M200KXD
(160 kVA/200 kVA) Models
Q4
Maintenance Bypass
S3M160KX/S3M160KXD
S3M200KX/S3M200KXD
(160 kVA/200 kVA) Models

Advertisement

Table of Contents
loading

Table of Contents