Overload Curves

2.10 Error Overload Low Speed

40
Load [%]
150%
105%
Permanent
current
(0 Hz)
At low speeds (below 3 Hz G-W housings, below 6Hz D-E housings), the rms current flowing
through the power transistors is higher, reaching 1.4 times the rated 60Hz rms value. This is
caused by the low-frequency sine wave created by the PWM. As a result, the continuous output
current must be limited at low speeds to prevent the power transistors from overheating. The
COMBIVERT F5 will drop the carrier frequency to 4kHz if necessary to be able to continue to
provide current to the motor. Once the output frequency rises above low frequency or the current
drops below the levels listed below, the carrier frequency will be returned to the higher value.
230V Maximum stall current (amps at 0Hz)
Inverter
Carrier
Housing
Frequency
13 14 15 15+ 16 17 17+ 19 20 21 23
E
8 kHz
24
16 kHz
16.8 16.8
G
8 kHz
16 kHz
H
8 kHz
16 kHz
R
8 kHz
16 kHz
U
4 kHz
8 kHz
16 kHz
480V Maximum stall current (amps at 0Hz)
Inverter
Carrier
Housing
Frequency
13 14 15 16 17 18 19 20 22 22+ 24 26 26+ 28
E
8 kHz
12 16.5 16
16 kHz
12
G
8 kHz
16 kHz
H
8 kHz
16 kHz
R
8 kHz
16 kHz
U
4 kHz
8 kHz
16 kHz
W
4 kHz
8 khz
16 kHz
E. OL2
0
Inverter Size
24
33
31
53
33
26
43
73 109 97
73
92
59
Inverter Size
10
10
19 22.0 21.5
8.4 9.5
-
42
50
54
25
30
36
E. OL
3 Hz
115 145 180
70 102 102
319
203
-
83
45
115 150
63
98
198 330 330
180 180 225
-
-
-
574
407
-