SECTION SEVEN – Troubleshooting
Heater Will Not Fire - C
Start
Is "SERVICE HEATER" LED
"on"?
YES
If any red diagnostic LED's
(AGS, AFS, SFS, HLS, PS, or
THERMISTOR) come "on", go
to to Page 7-7 and 7-8.
CONTINUE
Did burner fire at all?
YES
Go to "BURNER
TROUBLESHOOTING"
(Page 7-9)
Go to "HEATER WILL NOT
FIRE-D" (Page 7-6)
Replace Ignition Control
Module.
NO
Check for 24 VAC between
VAL and GND terminals on
Ignition Control Module.
SEE NOTE 1.
YES
Check for 24 VAC between
VAL and GND terminals on
Control Board. SEE NOTE 1.
NO
Fix wiring between VAL and
GND terminals of Ignition
Control Module and Control
Board.
NO
Turn off power to
heater for 5 seconds,
and turn back on.
Make sure tempera-
ture setting is above
water temperature.
NO
Wait one minute.
Does heater fire and
stay on?
NO
Did Blower come on?
Verify that gas is flow-
ing to burner during
ignition try. Observe
gas meter for move-
ment during ignition
YES
try (wait for about 30
seconds after calling
for heat).
Check for 24 VAC
between TH and GND
YES
terminals on Ignition
Control Module.
SEE NOTE 2.
Check for 24 VAC
between TH and GND
terminals on Control
Board. SEE NOTE 2.
YES
Check for 24 VAC
between GAS
terminals on Control
Board. SEE NOTE 1.
Replace Control
Board.
7-5
Go to "INITIAL
TROUBLESHOOTING"
Continue to observe heater
for several minutes. Cycle
heater on and off several
times. Observe for delayed or
rough ignition, poor combus-
YES
tion, premature extinction of
flame, evidence of boiling, or
operation of any diagnostic
LED. Go to pertinent trou-
bleshooting section if any
malfunction is observed.
NO
Replace Control Board.
YES
NO
Verify that gas supply is open
all the way to gas valve, and
Gas Valve knob is at "on"
position.
Check for 24 VAC to Gas
NO
Valve terminals during ignition
try. (Voltage appears about 24
seconds after call for heat).
SEE NOTE 1.
Replace Gas Valve with
identical part.
Fix wiring between TH and
NO
YES
GND terminals of Ignition
Control Module and Control
Board.
NO
Replace Control Board.
Fix wiring between GAS
YES
terminals on Control Board
and Gas Valve.
NO
NOTE 1: Voltage appears immedi-
ately after call for heat, and may be
on for only about 30 seconds.
NOTE 2: Voltage appears about 24
seconds after call for heat, and may
be on for only about 7 seconds.