Download Print this page

Siemens N 262E11 Technical Product Information

Advertisement

Quick Links

Binary input device N 262E11
16x potential-free contacts
Product and function description
The N 262E11 binary input device is a 6 module units
wide DIN rail mounted device in N-System dimensions
with 16 inputs for potential-free contacts. It enables both
statuses (contact is open or closed) and changes in status
(contact became opened or closed) to be recorded by
means of voltage impulses generated inside of the de-
vice. It can therefore be used, for example, to monitor
the switching or operating states (whether a device or a
plant is switched on or off, whether a limit violation or a
malfunction or an alarm is being signalled), to record the
change of status when switching on or switching off
(whether a switch or a pushbutton was activated,
whether it was activated for a shorter or longer period)
and to record and count changes of the switching status
(i.e. pulses) with a minimum on-time of the contact of 70
ms and a max. pulse succession of up to 5 pulses per
second, without or with monitoring of the number of
pulses counted until a predetermined threshold has been
reached or exceeded.
At each input a red LED shows whether the connected
contact is open (LED is off) or closed (LED is illuminated).
The N 262E11 has an integrated 230 V power supply in
order to supply the electronics. This power supply en-
ables the generation of the voltage pulses for checking
the switching statuses and for displaying them via the
LEDs even when there is no bus voltage present.
Note: The device is without function after the application
program has been "unloaded" with the ETS. The status of
the inputs is also no longer displayed in this case.
Application program
The "25S16 Binary Input Device 980D03" application pro-
gram, which can be downloaded with the ETS3.0f, sup-
Siemens AG
Infrastructure & Cities Sector, Building Technologies
Control Products and Systems
P.O. Box 10 09 53, D-93009 Regensburg
ports a multitude of applications and enables one of the
following functions to be assigned to every input:
- Switching status / binary value transmission
- Switching, edge-triggered
- Switching, short / long operation
- 1-button dimming
- 1-button solar protection control
- 1-button group control (sequence control)
- 1-bit Scene control
- 8-bit Scene control
- 8-bit value, edge-triggered
- 8-bit value, short / long operation
- 16-bit floating point value, edge-triggered
- 16-bit floating point value, short / long operation
- 8-bit pulse counting without threshold check
- 8-bit pulse counting with threshold check
- 16-bit pulse counting without threshold check
- 16-bit pulse counting with threshold check
- 32-bit pulse counting without threshold check
- 32-bit pulse counting with threshold check.
Using the ETS, one of the following functions can be al-
located to one input pair, i.e. to two neighbouring in-
puts:
- 2-button dimming with stop telegram
- 2-button solar protection control.
Connection example
N 262E11, 4 pages
Siemens AG 2013
Subject to change without further notice
GAMMA instabus
Technical Product Information
August 2013
5WG1 262-1EB11
A
A
B
B
C
C
D
D
E
E
g
g
h
h
N 262E11
230 V AC
Technical Manual
Update: http://www.siemens.com/gamma
2.7.4.2/1

Advertisement

loading

Summary of Contents for Siemens N 262E11

  • Page 1 - 16-bit pulse counting with threshold check - 32-bit pulse counting without threshold check The N 262E11 binary input device is a 6 module units - 32-bit pulse counting with threshold check. wide DIN rail mounted device in N-System dimensions with 16 inputs for potential-free contacts.
  • Page 2 GAMMA instabus Technical Product Information August 2013 Binary input device N 262E11 5WG1 262-1EB11 16x potential-free contacts Installation notes Inputs 16 inputs, potential-free (with basic insulation 250 V The device can be used for permanent installation in against each other and against the EIB)
  • Page 3 The bus terminal (D2) is located on the upper side of Figure 1: Position of the display and operating elements the binary input device N 262E11 (D1). The bus terminal (D2) consists of two sections (D2.1, A1 Button for toggling between normal mode / ad- D2.2) each with four terminal contacts.
  • Page 4 Any faulty device is to be sent together with a return de- The locating clamp (E3) encloses the contact system livery note of the local Siemens office. (E2) on the rear of the device (E1). If you have further questions concerning the product Insert the screwdriver between the DIN rail mounted please contact our technical support.

This manual is also suitable for:

5wg1 262-1eb11 5wg1 262-1eb11