Checking Low Pressure Control; Checking Capacitor; Testing Start Relay Kits - Daikin APGM3 Service And Troubleshooting

13.4 seer2 & 15.2 gas-electric package units with r-410a refrigerant
Table of Contents

Advertisement

SERVICING

Checking Low Pressure Control

The low pressure control senses the pressure in the
suction line and will open its contacts on a drop in
pressure. The low pressure control will automatically reset
itself with a rise in pressure.
The low pressure control is designed to cut-out (open) at
approximately 55 PSIG ± 7 PSIG. It will automatically cut-in
(close) at approximately 95 PSIG ± 7 PSIG.
Test for continuity using a VOM and if not as above,
replace the control.

Checking Capacitor

Capacitor, Run
A run capacitor is wired across the auxiliary and main
windings of a single phase permanent split capacitor
motor. The capacitors primary function is to reduce the line
current while greatly improving the torque characteristics
of a motor. This is accomplished by using the 90° phase
relationship between the capacitor current and voltage
in conjunction with the motor windings so that the motor
will give two phase operation when connected to a single
phase circuit. The capacitor also reduces the line current to
the motor by improving the power factor.
Capacitor, Start
Scroll Compressor Models
Hard start components are not required on Scroll
compressor equipped units due to a non-replaceable check
valve located in the discharge line of the compressor.
However hard start kits are available and may improve low
voltage starting characteristics.
This check valve closes off high side pressure to the
compressor after shut down allowing equalization through
the scroll flanks. Equalization requires only about one or
two seconds during which time the compressor may turn
backwards.
Your unit comes with a 180-second anti-short cycle
to prevent the compressor from starting and running
backwards.
Models Equipped With A Hard Start Device
A start capacitor is wired in parallel with the run capacitor
to increase the starting torque. The start capacitor is of the
electrolytic type, rather than metallized polypropylene as
used in the run capacitor.
A switching device must be wired in series with the
capacitor to remove it from the electrical circuit after the
compressor starts to run. Not removing the start capacitor
will overheat the capacitor and burn out the compressor
windings.
These capacitors have a 15,000 ohm, 2 watt resistor
wired across its terminals. The object of the resistor
is to discharge the capacitor under certain operating
conditions, rather than having it discharge across the
closing of the contacts within the switching device such as
the Start Relay, and to reduce the chance of shock to the
servicer. See the Servicing Section for specific information
concerning capacitors.
Relay, Start
A potential or voltage type relay is used to take the start
capacitor out of the circuit once the motor comes up to
speed. This type of relay is position sensitive. The normally
closed contacts are wired in series with the start capacitor
and the relay holding coil is wired parallel with the start
winding. As the motor starts and comes up to speed, the
increase in voltage across the start winding will energize
the start relay holding coil and open the contacts to the
start capacitor.

TESTING START RELAY KITS

Testing Coil Relay
1. Disconnect power to unit.
2. Disconnect all wiring.
3. Measure the resistance of the coil between terminals
2 & 5.
4. If the coil reads open or shorted, replace the relay.
Testing Start Relay Coil Resistance
Testing Relay Contacts
Testing Contacts Resistance
a. Disconnect power to unit.
b. Disconnect all wiring to the start relay.
c. Measure the resistance of the contacts between
terminals 1 & 2.
d. If the contacts read open, replace the relay.
Testing Contacts Voltage
a. With power on, provide a call for cool to energize
the compressor.
b. With the compressor running, use a voltmeter to
measure the voltage between terminals 1 & 2.
c. Voltage reading of zero indicates that the relay's
contacts are stuck, replace the relay.
17

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gpgm3Apgm5Gpgm5

Table of Contents