Settings Menu
CONFIGURATION > FUNCTION CONFIG
Parameter
Gn Derived E/F
CONFIGURATION > CURRENT PROT'N > DERIVED E/F > 51N-n
Parameter
Gn 51N-n Element
Gn 51N-n Setting
Gn 51N-n Char
Gn 51N-n Time Mult
(Applicable when Gn
51N-n Char is IEC/
ANSI)
Gn 51N-n Delay
(Applicable when Gn
51N-n Char is DTL)
Gn 51N-n MinO-
perate
Gn 51N-n Follower
DTL
Gn 51N-n Reset
Gn 51N-n Inrush
Action
Information List
Input/Output Matrix User Logic
Inhibit 51N-n
51N-n
Reyrolle, 7SR45, Device Manual
C53000-G7040-C101-2, Edition 09.2020
Setting Options
Disabled
Enabled
Setting Options
Disabled
Enabled
0.10 ⋅ I
to 0.80 ⋅ I
rated
rated
Δ 0.01 ⋅ I
rated
IEC-NI
DTL
ANSI-EI
ANSI-VI
ANSI-MI
IEC-LTI
IEC-EI
IEC-VI
0.01 to 10.00
Δ 0.01
0.00s to 15.00 s
Δ 0.01 s
0.00 s to 20.00 s
Δ 0.01 s
0.00 s to 20.00 s
Δ 0.01 s
IEC/ANSI Decay
00 s to 60 s
Δ 1 s
Off
Inhibit
Type
Inhibit 51N-n
Input
51N-n
Output
3.5 Time-Delayed Derived Earth Fault Protection (51N)
Settings
Default
Gn1
Disabled
Settings
Default
Gn1
Disabled
0.50 ⋅ I
rated
IEC-NI
1.00
5.00 s
0.00 s
0.00 s
00 s
Off
IEC 103
Y
Functions
Gn2
Gn2
Modbus RTU
Y
57