Device Functionality
2.3 Binary Outputs
Parameters
General Pickup
9
IL1 / A
IL2 / B
9
IL3 / C
9
IE / E
9
Prot'n Healthy
Low Battery
IRF
Local mode
8
Remote mode
8
Out of Service mode
BI1 Operated
BI2 Operated
10
BI3 Operated
BI4 Operated
10
Reclose Inhibit
NOTE
i
i
If a binary output is assigned to IRF, do not use the same binary output for any other functions.
NOTE
i
i
The Reclose Inhibit parameter is only available in dual powered variants. Siemens recommends
configuring this parameter with permanent auxiliary power.
Binary Output Operations
The relay reset can be performed from the Relay Identifier Screen > TEST/RESET▶ key.
If the fault current persists and if you press the TEST/RESET▶ key, then the pop-up message appears, FAULT
PERSISTS.
Based on the availability of the power source, the flag can be reset using any one of the following conditions:
BO Trip/Reset on Battery/USB
In this mode, the relay uses the power from the battery/USB to operate or reset the binary output and takes
approximately 4 s.
If the consecutive commands are provided within 4 s, then the relay performs delayed operations and displays
INSUFFICIENT ENERGY as a pop-up message on the HMI.
BO Trip/Reset on CT Input or Auxiliary Voltage
In this mode, the relay can operate or reset the binary outputs instantaneously.
BO cannot be mapped to IL1 / A, IL2 / B, IL3 / C & IE / E. The HMI will display X for these functions. In Reydisp Evolution, LED configu-
9
ration for these functions is disabled.
10
For all 7SR450[1/3] variants, this parameter is not not available.
30
Description
Pickup detected
Phase A tripped
Phase B tripped
Phase C tripped
Phase E tripped
Protection healthy
Battery volts low indica-
tion
Internal relay failure
Local mode
Remote mode
Out of service mode
8
BI1 operated
BI2 operated
BI3 operated
BI4 operated
Interlock for reclose of
8
CB after 49 trip
Default
Min
Value
X
X
X
X
1 (BO1), –
(Others)
C53000-G7040-C101-2, Edition 09.2020
Max
Step Change
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Reyrolle, 7SR45, Device Manual